Plan Review Notes
Plan Review Notes For Permit 06021135
Permit Number 06021135
Review Stop M
Sequence Number 4
Notes
Date Text
2006-10-10 08:59:52MECHANICAL REVISION
 *** DENIED ***
  
 1) SEE MECHANICAL PLANS A/C SYSTEMS #2
 AND #3 SENSIBLE BTU'S CAN NOT BE MORE
 THAN 20% OVER THE MANUAL J CALCULATIONS,
 SEE ATTACHED COPY OF MANUAL J CAL'S.
 PLEASE CORRECT OR SUBMIT REVISED MANUAL J
 CAL'S. PER 2004 FBC 13-607.1.ABC.1.1 .
  
 2) RETURN AIR TRANSFER DUCTS TO AC #4
 FROM THE FAMILY ROOM ARE TO SMALL, SEE
 NOTE # 5, PLEASE CORRECT.
  
 3) A 10" RETURN AIR DUCT TO THE MASTER
 SUITEIS TO SMALL FOR A 12" SUPPLY AIR
 DUCT, ALL AIR TO THE MASTER SUITE MUST
 BE INCLUDED, SEE NOTE #5 (C) EXCEPT.
 PLEASE CORRECT.
  
 4) TWO SUPPLY AIR DUCTS IN THE DEN ARE
 NOT SIZED, PLEASE CORRECT.
  
 5) BALANCED RETURN AIR.
 THIS MAY BE ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY
 INCREASING THE RETURN TRANSFER ONE AND
 ONE HALF TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING
 AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE
 PROPER RETURN AIR BALANCE.
 (B)TRANSFER GRILLES SHALL USE 50
 SQUARE INCHES (OF GRILLE AREA) TO 100
 CFM (OF SUPPLY AIR) FOR SIZING
 THROUGH-THE-WALL TRANSFER GRILLES AND
 USING AN UNRESTRICTED 1-INCH
 UNDERCUTTING OF DOORS TO ACHIEVE PROPER
 RETURN AIR BALANCE
 (C)HABITABLE ROOMS ONLY SHALL BE
 REQUIRED TO MEET THESE REQUIREMENTS FOR
 PROPER BALANCED RETURN AIR EXCLUDING
 BATHROOMS, CLOSETS, STORAGE ROOMS AND
 LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY
 AIR INTO THE MASTER SUITE SHALL BE
 INCLUDED. PER 2004 FBC/R M1602.4 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.