2006-10-10 08:59:52 | MECHANICAL REVISION |
| *** DENIED *** |
| |
| 1) SEE MECHANICAL PLANS A/C SYSTEMS #2 |
| AND #3 SENSIBLE BTU'S CAN NOT BE MORE |
| THAN 20% OVER THE MANUAL J CALCULATIONS, |
| SEE ATTACHED COPY OF MANUAL J CAL'S. |
| PLEASE CORRECT OR SUBMIT REVISED MANUAL J |
| CAL'S. PER 2004 FBC 13-607.1.ABC.1.1 . |
| |
| 2) RETURN AIR TRANSFER DUCTS TO AC #4 |
| FROM THE FAMILY ROOM ARE TO SMALL, SEE |
| NOTE # 5, PLEASE CORRECT. |
| |
| 3) A 10" RETURN AIR DUCT TO THE MASTER |
| SUITEIS TO SMALL FOR A 12" SUPPLY AIR |
| DUCT, ALL AIR TO THE MASTER SUITE MUST |
| BE INCLUDED, SEE NOTE #5 (C) EXCEPT. |
| PLEASE CORRECT. |
| |
| 4) TWO SUPPLY AIR DUCTS IN THE DEN ARE |
| NOT SIZED, PLEASE CORRECT. |
| |
| 5) BALANCED RETURN AIR. |
| THIS MAY BE ACHIEVED BY. |
| (A)TRANSFER DUCTS MAY ACHIEVE THIS BY |
| INCREASING THE RETURN TRANSFER ONE AND |
| ONE HALF TIMES THE CROSS SECTIONAL AREA |
| (SQUARE INCHES) OF THE SUPPLY DUCT |
| ENTERING THE ROOM OR SPACE IT'S SERVING |
| AND THE DOOR HAVING AT LEAST AN |
| UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE |
| PROPER RETURN AIR BALANCE. |
| (B)TRANSFER GRILLES SHALL USE 50 |
| SQUARE INCHES (OF GRILLE AREA) TO 100 |
| CFM (OF SUPPLY AIR) FOR SIZING |
| THROUGH-THE-WALL TRANSFER GRILLES AND |
| USING AN UNRESTRICTED 1-INCH |
| UNDERCUTTING OF DOORS TO ACHIEVE PROPER |
| RETURN AIR BALANCE |
| (C)HABITABLE ROOMS ONLY SHALL BE |
| REQUIRED TO MEET THESE REQUIREMENTS FOR |
| PROPER BALANCED RETURN AIR EXCLUDING |
| BATHROOMS, CLOSETS, STORAGE ROOMS AND |
| LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY |
| AIR INTO THE MASTER SUITE SHALL BE |
| INCLUDED. PER 2004 FBC/R M1602.4 . |
| |
| MECHANICAL PLAN REVIEW BY; |