2006-11-14 13:52:15 
  
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT.
  
 1} THE APPARANT DISCONNECTS, MISMARKED PANEL"A" AND
 "B" ON THE RISER DIAGRAM,ARE NOT LOCATED ON THE PLAN.
 LOCATE SAME. PANELS "A & B" IN THE LAUNDRY ROOM ARE IN
 VIOLATION OF 225.32, LOCATION OF DISCONNECTS.
  
 2} THE PANELS ON THE RISER DIAGRAM ARE NOT ALL
 DESIGNATED AND DO NOT CORRELATE WITHE THE PANEL
 SCHEDULES WHICH ARE NOT MARKED EITHER, EXCEPT TWO THAT
 ARE BOTH MARKED "A". PLEASE MARK ALL PANELS AND
 DISCONNECTS, SEE PERMIT SET.
  
 3} CORRELATE THE DISCONNECT AND PANEL RATINGS ON THE
 RISER WITH THE SAME ON PANEL SCHEDULES. NOTE THATTHE
 PANELS MARKED "A" ARE LISTED AS 150 AMP.
  
 4} THERE ARE NO EQUIPMENT GROUNDS, REQUIRED PER
 250.122, RAN TO ANY PANELS FROM THE DISCONNECTS, EXCEPT
 THE GARAGE PANEL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.