2006-04-28 00:00:00 | *** DENIED *** |
| 1) MANUAL J CALCULATIONS ARE CALLING FOR |
| A TOTAL OF 25,892 SENSIBLE BTU'S, |
| MECHANICAL PLANS ARE CALLING FOR A TOTAL |
| OF 47,800 SENSIBLE BTU'S, THE PLANS CAN |
| ONLY CALL FOR 20% MORE THAN THE MANUAL J |
| CAL'S PLEASE CORRECT, PER 2004 FBC CH. |
| 13, 607.1.ABC.1.1 . |
| |
| 2) PLEASE CORRECT THE FLOOR SIZE FOR |
| ZONE 1 IN THE MANUAL J CAL'S. |
| |
| 3) A 12" RETURN AIR DUCT TO AHU #3 |
| APPEARS TO SMALL BOR A 3 TON A/C SYSTEM, |
| PLEASE CORRECT. |
| |
| 4)PLEASE SHOW THE SIZE OF THE R/A RIDGE |
| DUCT IN A/C CLOSET #3. |
| |
| 5)RETURN AIR TRANSFER DUCT TO FAMILY |
| ROOM IS UNDER SIZED, SEE NOTE #7. |
| |
| 6) AS REQUESTED 3-14-06 #7, RETURN AIR |
| TRANSFER DUCT TO MASTER BEDROOM IS UNDER |
| SIZED, SEE NOTE #7 (C) EXCEPT.. |
| |
| 7)BALANCED RETURN AIR. |
| THIS MAY BE ACHIEVED BY. |
| (A)TRANSFER DUCTS MAY ACHIEVE THIS BY |
| INCREASING THE RETURN TRANSFER ONE AND |
| ONE HALF TIMES THE CROSS SECTIONAL AREA |
| (SQUARE INCHES) OF THE SUPPLY DUCT |
| ENTERING THE ROOM OR SPACE IT'S SERVING |
| AND THE DOOR HAVING AT LEAST AN |
| UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE |
| PROPER RETURN AIR BALANCE. |
| (B)TRANSFER GRILLES SHALL USE 50 |
| SQUARE INCHES (OF GRILLE AREA) TO 100 |
| CFM (OF SUPPLY AIR) FOR SIZING |
| THROUGH-THE-WALL TRANSFER GRILLES AND |
| USING AN UNRESTRICTED 1-INCH |
| UNDERCUTTING OF DOORS TO ACHIEVE PROPER |
| RETURN AIR BALANCE |
| (C)HABITABLE ROOMS ONLY SHALL BE |
| REQUIRED TO MEET THESE REQUIREMENTS FOR |
| PROPER BALANCED RETURN AIR EXCLUDING |
| BATHROOMS, CLOSETS, STORAGE ROOMS AND |
| LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY |
| AIR INTO THE MASTER SUITE SHALL BE |
| INCLUDED. PER 2004 FBC/R M1602.4 . |
| |
| MECHANICAL PLAN REVIEW BY; |
| TOM GORDON (561) 805-6729. |