Text |
2006-03-14 00:00:00 | *** DENIED *** |
| 1) ARCHITECT'S LICENSE NUMBER MUST |
| APPEAR IN THE TITLE BLOCK, PER FAC |
| 61G1-16.004 . |
| |
| 2) ENERGY CALCULATIONS NEED TO BE SIGNED |
| BY OWNER/AGENT. |
| |
| 3) PLEASE SHOW TOTAL COOLING BTU'S. AND |
| SENSIBLE COOLING BTU'S. ON MECHANICAL |
| PLANS. |
| |
| 4) PLANS ARE SHOWING AN EXHUST FAN IN |
| THE LAUNDRY ROOM WITH A GAS WATER |
| HEATER, THIS WILL REMOVE THE COMBUSTION |
| AIR FROM THE ROOM PLEASE CORRECT. |
| |
| 5) PLEASE SHOW THE SIZE OF THE RETURN |
| AIR GRILL TO AHU #4. |
| |
| 6) RETURN AIR TRANSFER DUCTS TO THE DEN. |
| AND PLAYROOM ARE UNDER SIZED, SEE NOTE |
| #8 (A). |
| |
| 7) RETURN AIR TRANSFER DUCT TO THE |
| MASTER SUITE IS TO SMALL, SEE NOTE #8 |
| (A) AND (C) "EXCEPT". |
| |
| 8)BALANCED RETURN AIR. |
| THIS MAY BE ACHIEVED BY. |
| (A)TRANSFER DUCTS MAY ACHIEVE THIS BY |
| INCREASING THE RETURN TRANSFER ONE AND |
| ONE HALF TIMES THE CROSS SECTIONAL AREA |
| (SQUARE INCHES) OF THE SUPPLY DUCT |
| ENTERING THE ROOM OR SPACE IT'S SERVING |
| AND THE DOOR HAVING AT LEAST AN |
| UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE |
| PROPER RETURN AIR BALANCE. |
| (B)TRANSFER GRILLES SHALL USE 50 |
| SQUARE INCHES (OF GRILLE AREA) TO 100 |
| CFM (OF SUPPLY AIR) FOR SIZING |
| THROUGH-THE-WALL TRANSFER GRILLES AND |
| USING AN UNRESTRICTED 1-INCH |
| UNDERCUTTING OF DOORS TO ACHIEVE PROPER |
| RETURN AIR BALANCE |
| (C)HABITABLE ROOMS ONLY SHALL BE |
| REQUIRED TO MEET THESE REQUIREMENTS FOR |
| PROPER BALANCED RETURN AIR EXCLUDING |
| BATHROOMS, CLOSETS, STORAGE ROOMS AND |
| LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY |
| AIR INTO THE MASTER SUITE SHALL BE |
| INCLUDED. PER 2004 FBC/R M1602.4 . |
| |
| MECHANICAL PLAN REVIEW BY; |
| TOM GORDON (561) 805-6729. |
| |