2006-06-16 00:00:00 | **UNSAT ** 2ND REVIEW** |
| |
| PLEASE SEE SOME COMMENTS FROM PREVIOUS |
| REVIEW AND SOME NEW COMMENTS DUE TO |
| PLANS SUBMITTED. |
| |
| 1) NOTE: PLEASE CORRELATE RISER DIAGRAM |
| WITH PANEL SCHEDULE FOR MDP. PLEASE SEE |
| T-1. |
| 215.5 |
| |
| 2) NOTE: PLEASE INDICATE ALL GROUNDING |
| ATTACHMENTS FOR THE TRANSFORMERS ARE |
| REQUIRED PER 250.30,250.66 ETC. |
| PLEASE SEE T-1 DOES NOT INDICATE THIS |
| ATTACHMENT.? |
| |
| 3) NOTE: PLEASE SEE 450.3 FOR MAX OCP |
| FOR THE TRANSFORMERS AS SHOWN TO BE |
| 125%. |
| PLEASE SEE MDP 70A 60A FOR T-1 AND PP |
| RISER SHOWS 60A FOR T-2. |
| PLEASE SEE RISER FOR T-2, IS THIS A |
| 3-POLE DISC WITH ONLY 2-PHASE'S BEING |
| USED? |
| THIS IS BEING ASSUMED AT THIS TIME, BUT |
| PLEASE CLARIFY. |
| PLEASE SEE DISC NOTE #3, 70A'S?? |
| PLEASE CORRELATE AT STATED IN NOTE #1 |
| ABOVE. |
| |
| 4) NOTE: PLEASE SEE THE CODES ON 1-E-1 |
| SHALL BE REFLECTED TO THE 2004 FBC AND |
| THE 2002 NEC. |
| |
| 5) NOTE: PLEASE SEE A NOTE OR |
| INFORMATION COULD NOT BE LOCATED |
| DENOTING ANY CLASS LOCATIONS. |
| |
| ** PLEASE SEE BUILDING REVIEW COMMENTS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |