Plan Review Notes
Plan Review Notes For Permit 06021125
Permit Number 06021125
Review Stop E
Sequence Number 2
Notes
Date Text
2006-06-16 00:00:00**UNSAT ** 2ND REVIEW**
  
 PLEASE SEE SOME COMMENTS FROM PREVIOUS
 REVIEW AND SOME NEW COMMENTS DUE TO
 PLANS SUBMITTED.
  
 1) NOTE: PLEASE CORRELATE RISER DIAGRAM
 WITH PANEL SCHEDULE FOR MDP. PLEASE SEE
 T-1.
 215.5
  
 2) NOTE: PLEASE INDICATE ALL GROUNDING
 ATTACHMENTS FOR THE TRANSFORMERS ARE
 REQUIRED PER 250.30,250.66 ETC.
 PLEASE SEE T-1 DOES NOT INDICATE THIS
 ATTACHMENT.?
  
 3) NOTE: PLEASE SEE 450.3 FOR MAX OCP
 FOR THE TRANSFORMERS AS SHOWN TO BE
 125%.
 PLEASE SEE MDP 70A 60A FOR T-1 AND PP
 RISER SHOWS 60A FOR T-2.
 PLEASE SEE RISER FOR T-2, IS THIS A
 3-POLE DISC WITH ONLY 2-PHASE'S BEING
 USED?
 THIS IS BEING ASSUMED AT THIS TIME, BUT
 PLEASE CLARIFY.
 PLEASE SEE DISC NOTE #3, 70A'S??
 PLEASE CORRELATE AT STATED IN NOTE #1
 ABOVE.
  
 4) NOTE: PLEASE SEE THE CODES ON 1-E-1
 SHALL BE REFLECTED TO THE 2004 FBC AND
 THE 2002 NEC.
  
 5) NOTE: PLEASE SEE A NOTE OR
 INFORMATION COULD NOT BE LOCATED
 DENOTING ANY CLASS LOCATIONS.
  
 ** PLEASE SEE BUILDING REVIEW COMMENTS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]