Plan Review Notes
Plan Review Notes For Permit 06021125
Permit Number 06021125
Review Stop E
Sequence Number 1
Notes
Date Text
2006-03-29 00:00:00************** UNSAT ***************
  
 1) NOTE: PLEASE LIST CURRENT CODES IN
 EFFECT, NFPA-70 2002, NFPA-101 2003.
  
 2) NOTE: PLEASE SEE SERVICE GROUNDING
 ELECTRODE SYSTEM. SHOWS BLDG STEEL, IS
 THIS NOT THE FOOTER STEEL OR IS THERE
 BOTH? IF BOTH THEN FOOTER STEEL WILL
 ALSO BE REQUIRED. IF NO "BLDG STEEL",
 PLEASE CALL OUT FOR FOOTER STEEL.
 250.50
  
 3) NOTE: PLEASE SEE GROUNDING ELECTRODE
 SYSTEM AT TRANSFORMER PER 250.30,250.66.
 PLEASE INCLUDE SIZE OF THE GEC.
 215.5
  
 4) NOTE: PLEASE SEE MAX OCP FOR
 TRANSFORMER SHALL BE BASED ON 450.3
 PLEASE KNOW, THE KVA FOR T-2 IS NOT
 CLEAR, A MODEL # IS SHOWN WHICH TENDS TO
 LEAD TO THIS TRANSFORMER AS ALSO BEING
 25 KVA? IF SO, IN EITHER CASE PLEASE SEE
 450.3 FOR MAX OCP.
 125%).
  
 5) NOTE: PLEASE SEE T-2, AND SEE 240.21,
 RISER SHOWS "TAPPING" A "TAP". PLEASE
 KNOW THIS NOT PERMITTED. A TAP SHALL
 TERMINTE IN A SINGLE MEANS OF OCP.
 215.5
  
 6) NOTE: PLEASE SEE 250.6,250.24B. AN
 "EQUIPMENT GROUNDING CONDUCTOR" IS BEING
 SHOWN FROM METER TO THE FIRST MEANS OF
 DISCONNECT FOR MDP SERVICE.
 PLEASE KNOW, THIS SHALL ONLY BE
 INSTALLED AFTER THE FIRST MEANS OF
 DISCONNECT.
 215.5
  
 7) NOTE: PLEASE SEE SEE CONDUCTORS AND
 CONDUIT SHOWN ON MDP RISER FOR FEED TO
 T-1??
 SEEMS TO BE AN ERROR/ OR MISPRINT.
 215.5
  
 8) NOTE: PLEASE SPECIFY ANY AREAS PER
 NEC ART 500.
 PLEASE LIST ANY AREA CHEMICAL FOR FUEL,
 MIXING ETC WHICH MAY CREATE AN CLASS
 LOCATION. PLEASE LIST OR SHOW.
  
 9) NOTE: PLEASE SPECIFY DEPT OF CONDUITS
 PER 300.5 IN AREAS ON SITE PLANS E-1
  
 PLEASE SEE NAY COMMENTS FROM OTHER
 TRADES WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW
 REVISED SHEETS INTO COMPLETE SETS FOR
 REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  