Plan Review Notes
Plan Review Notes For Permit 06021020
Permit Number 06021020
Review Stop M
Sequence Number 1
Notes
Date Text
2006-02-27 00:00:00*** DENIED ***
 1) PLANS MUST SHOW NAME OF COMPANY,
 ADDRESS, PHONE NUMBER, AND LIC. NUMBER.
  
 2)ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 SHALL BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN. PER
 FBC 104.2.1 .
  
 3) PLEASE SHOW SIZE OF GRILLS ON PLANS.
  
 4) PLEASE SHOW SIZE OF RETURN AIR
 TRANSFER GRILLS AND OR RETURN AIR DUCTS.
  
 5) PLEASE SHOW LOCATION OF AHU (CLOSET
 OR ATTIC ?).
  
 6) PLEASE SHOW LOCATION AND SIZE OF MAIN
 RETURN AIR GRILL (AND DUCT ?).
  
 7) PLEASE SHOW CONDENSATE DRAIN LINE ON
 PLANS (AND COPPER LINE SIZES).
  
 8) PLEASE EXPLAIN WHY YOU ARE USING A
 14" SUPPLY AIR DUCT TO THE LIVING ROOM
 GRILL FOR A RESIDENTIAL APPLICATION,
 WHEN IT IS NOT RECOMMENDED, IF THE ROOM
 IS THAT LARGE TWO OR THREE SMALLER DUCT
 WOULD BE APPROPRIATE.
  
 9) PLEASE LIST A/C EQUIPMENT ON
 MECHANICAL PLANS ALSO (NOT JUST ON
 MANUAL 'J').
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.