2006-08-08 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 FROM PREVIOUS REVIEW:
  
 1.)ADDRESSED.
  
 2.)DECLARE OCCUPANCY, FBC3.
 PLEASE DECLARE ONE OF THE OCCUPANCY
 CLASSIFICATIONS IN THIS CHAPTER, SEE
 FBC3310.BASED ON YOUR DESCRIPTION OF
 USE, IT APPEARS TO BE R2.
  
 ALL OTHER COMMENTS BELOW NOT ADDRESSED
  
 3.)SPECIFY FLOORING ON THE PLAN.SHOW
 COMPLIANCE WITH FBC1207.
  
 4.)ARE ALL FLOOR FINISHES TILE?ARE
 ANY CARPET?SEE FBC EB503.2.NOTE -
 ADDRESSED; TILE FLOORING.
  
 5.)PROVIDE FIRE RESISTANCE
 INFORMATION, EITHER RATED ASSEMBLY OR
 SHOW CALCULATED FIRE RESISTANCE, FOR THE
 TENANT SEPARATIONS BOTH HORIZONTAL AND
 VERTICAL.
  
 6.)ENERGY CALCS ARE NO LONGER IN THE
 PACKAGE.
  
 7.)SPECIFY INTERIOR FINISH
 CLASSIFICATION, FBC EB503.1, FBC803.5.
  
 8.)THE PLANS SHOW LAUNDRY FACILITIES
 UNDER THE STAIRS.WAS THIS PERMITTED?
 PROVIDE PERMIT INFORMATION, PLUMBING AND
 ELECTRIC.
  
 NEW COMMENT:
  
 SEE ATTACHED FS553.80(2)(B).