Plan Review Notes For Permit 06021006 |
Permit Number |
06021006 |
|
Review Stop |
E |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2006-09-19 00:00:00 | | | | | NONCOMPLIANT | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIEW. | | | | 1} THE SERVICE CONDUCTORS ARE NOT LARGE | | ENOUGH FOR THE CALCULATD LOAD. SEE TABLE | | 310.16, 250 MCM IS REQUIRED FOR 240 | | AMPS. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | | | | | | | |
|