2006-09-19 00:00:00 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE SERVICE CONDUCTORS ARE NOT LARGE
 ENOUGH FOR THE CALCULATD LOAD. SEE TABLE
 310.16, 250 MCM IS REQUIRED FOR 240
 AMPS.
  