Date Text
2006-06-09 00:00:00 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1}THERE ARE FLOOR PLANS ON SHEET 3/5
 AND SHEET 5/5. REMOVE THE ONE NO TTO BE
 REVIEWED. PREFERABLE USE THE SCALE ON
 SHEET 3/5.
  
 2} THERE IS ONLY ONE FLOOR, TWO UNITS,
 ON THE PLAN. PROVIDE DRAWINGS FOR ALL
 UNITS AND INDICATE UNIT NUMBERS.
  
 3} THERE IS A SMOKE DETECTOR MISSING IN
 ONE UNIT, AND A KITCHEN GFI IN ANOTHER.
 UNITS HAVE NO DESIGNATIION, SEE REVIEWED
 PLAN FOR REDLINES.
  
 4} THERE IS A BATH GFI MISSING .
  
 5} THE PANEL SCHEDULE INDICATES ONE
 SMALL APPLIANCE CRCUIT AND THE CALC'S
 INDICATE THREE. SEE 210.11(C)(1).
  
 6} PLEASE LOCATE ALL SERVICE EQUIPMENT
 ON THE PLAN, METER ENCLOSURE,
 DISCONNECTS AND PANELS, SO THAT
 COMPLIANCE WITH ARTICLES 225 AND 230 CAN
 BE REVIEWED.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
  