2006-03-14 00:00:00DENIED
 REFERENCE: FBC-2004 R4101 SWIMMING POOLS
  
 PLEASE ADJUST YOUR NOTES, DETAILS, OR
 SUBMITTALS TO REFLECT THE FOLLOWING
 INFORMATION REQUIRED FOR PLAN REVIEW:
  
 1) COMPLY WITH FBC-2004 SEC. R4101 PRI-
 VATE SWIMMING POOLS. (ADD TO NOTES)
 2) PAGE 3 OF 4 STATES "MAXIMUM
 UNDERWATER LENGTH OF VENT PIPING 30
 FEET, PAGE 1 OF 4 VENT PIPE APPEARS TO
 BE LONGER THAN 30 FEET. PLEASE SUPPLY
 ENGINEERED TABLE FOR "VENT PIPE MAXIMUM
 LENGTH" INDICATING PUMP SIZE, AVERAGE
 FLOW (GPM), AND MAXIMUM LENGTH OF 1-1/2"
 PVC VENT PIPE, FROM WHERE IT STARTS TO
 WHERE IT TERMINATES. COMPLY WITH 3 SE-
 COND RELEASE.
 3) FBC-2004R4101.6.6.5 WHERE PROVIDED,
 THE VACUUM OR PRESSURE CLEANER FITTING
 SHALL BE LOCATED AT LEAST 6" AND NOT
 GREATER THAN 12" BELOW THE MINIMUM OPER-
 ATING WATER LEVEL OR AS AN ATTACHMENT TO
 THE SKIMMER.(ADD TO NOTES, AND DETAILS
 REQUIRED)
 4) FBC-2004 R4101.9 WATER SUPPLY, LOCAL
 ORD. #2853, BACKFLOW REQUIRED ON WATER
 SERVICE. (ADD TO NOTES)
 5) FBC-2004 R4101.14.1 SWIMMING POOL
 WATER HEATERS SHALL BEAR THE LABEL OF A
 RECOGNIZED TESTING AGENCY. MANUFACTURE
 SHEETS REQUIRED. (SUBMITTAL REQUIRED)
 6) FBC-2004 R4101.14.2 WATER RETENTION,
 PROVIDE A POSITIVE MEANS OF RETAINING
 WATER IN THE HEATER WHEN PUMP IS SHUT
 OFF.(MANUFACTURE CUT SHEETS SUBMITTAL
 REQUIRED)
 7) FBC-2004 R4101.15 GAS PIPING SHALL
 COMPLY WITH FBC-2004 FUEL GAS. SEPERATE
 PLANS AND PERMIT REQUIRED.(ADD TO NOTES)
  
 END OF COMMENTS:
  