Plan Review Notes For Permit 06020895 |
Permit Number |
06020895 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-03-17 00:00:00 | ******DENIED****** | | | | 1) PLEASE ILLUSTRATE THE LOCATIONS OF | | DUCT SMOKE DETECTORS. THE RISER DIAGRAM | | AND DRAWINGS INDICATE FIVE AC UNITS. | | | | 2) DUCT SMOKE DETECTORS SHALL INITIATE A | | GENERAL FIRE ALARM IN ACCORDANCE WITH | | LOCAL REQUIREMENTS. | | | | 3) FIRE ALARM TO BE UL CERTIFIED FOR | | CENTRAL STATION SERVICE. UL CERTIFICATE | | WILL BE REQUIRED AT TIME OF FIRE ALARM | | FINAL INSPECTION. | | | | 4) FIRE ALARM SYSTEM SHALL BE CLASS A, | | STYLE D OR FULLY ADDRESSABLE. | | | | 5) SIGNED, SEALED AND DATED PLANS HAVE | | BEEN SUBMITTED, HOWEVER COPIES HAVE BEEN | | PROVIDED. PLANS MUST COMPLY WITH FAC | | 61G15-23.001, AND MUST SHOW THE WORD | | "LICENSE" IN THE SEAL. | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | FIRE PLANS REVIEW (561) 805-6722 |
|