2006-03-10 00:00:00 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| |
| FBCFLORIDA BUILDING CODE 2004 |
| FBC EBEXISTING BUILDING |
| FBC R RESIDENTIAL |
| FBC* CITY OF WEST PALM BEACH |
| AMENDMENTS TO THE FBC2004 |
| |
| WINDOW OR DOOR PERMIT APPLICATION, ONLY |
| CHECKED ITEMS APPLY |
| |
| _XX_1.A NOTICE OF COMMENCEMENT MUST |
| BE FILED WITH THE CLERK OF COURTS BEFORE |
| A PERMIT CAN BE ISSUED, FS713.13. |
| |
| ____2.PROVIDE BUILDING HEIGHT. |
| DESIGN PRESSURES FOR BUILDINGS OVER |
| 60FEET ARE REQUIRED TO BE DESIGNED USING |
| ASCE7, FBC1609.1.1. DOCUMENTS PREPARED |
| BY AN ENGINEER AND SUBMITTED FOR PUBLIC |
| RECORD ARE TO BE SIGNED SEALED ORIGINALS |
| FAC61G15-23.002. |
| |
| ____3.PROVIDE A COPY OF THE CONDO |
| ASSOCIATION APPROVAL. |
| |
| _XX_4.IMPACT PROTECTION REQUIRED, |
| FBC EB507.3, FBC1609.1.4. |
| |
| _XX_5.FLORIDA STATE OR LOCAL PRODUCT |
| APPROVAL REQUIRED, FAC9B72, |
| WWW.FLORIDABUILDING.ORG. |
| THE STATE PRODUCT APPROVALS SUBMITTED |
| EXPIRED WHEN THE CODE CHANGED.ALSO |
| STATE PRODUCT APPROVALS WERE NOT |
| SUBMITTED FOR THE HORIZONTAL ROLLER AND |
| THE EGRESS WINDOW. |
| |
| ____6.PROVIDE A FLOOR PLAN SHOWING |
| BEDROOM LOCATIONS.SHOW THAT EMERGENCY |
| EGRESS REQUIREMENTS OF FBC R310.1 HAVE |
| BEEN MET. |
| |
| _XX_ 7.SCOPE OF WORK IS NOT CLEAR. |
| THE FLOOR PLAN STATES THAT HR WINDOWS |
| WILL BE INSTALLED AT BEDROOM LOCATIONS, |
| SO WHY WERE EGRESS WINDOW PRODUCT |
| APPROVALS ALSO SUBMITTED?PRODUCT |
| APPROVALS FOR MULLIONS SUBMITTED AND |
| APPEAR ON THE MATERIAL ORDER; NO DOUBLE |
| WINDOWS SHOWN ON THE PLAN. |