Plan Review Notes
Plan Review Notes For Permit 06020819
Permit Number 06020819
Review Stop G
Sequence Number 2
Notes
Date Text
2006-03-16 00:00:00PAUL SCHMITZ
 [email protected]
 FBC 2004 PLUMBING CODE PLAN REVIEW
 FBC2004 FUEL GAS CODEPLAN REVIEW
 FBC 2004 CH 11, FL ACESSIBILITY CODE
 DENIED
  
 1) GAS WATER HEATERS LOCATED IN CLOSETS
 IN EACH UNIT NOT APROVED.
 SECTION 303 APPLIANCE LOCATION
 303.1 GENERAL.
 APPLIANCES SHALL BE LOCATED AS REQUIRED
 BY THIS SECTION, SPECIFIC REQUIREMENTS
 ELSEWHERE IN THIS CODE AND THE
 CONDITIONS OF THE EQUIPMENT AND
 APPLIANCE LISTING.
 303.2 HAZARDOUS LOCATIONS.
 APPLIANCES SHALL NOT BE LOCATED IN A
 HAZARDOUS LOCATION UNLESS LISTED AND
 APPROVED FOR THE SPECIFIC INSTALLATION.
 303.3 PROHIBITED LOCATIONS.
 APPLIANCES SHALL NOT BE LOCATED IN, OR
 OBTAIN COMBUSTION AIR FROM, ANY OF THE
 FOLLOWING ROOMS OR SPACES:
 1. SLEEPING ROOMS.
 2. BATHROOMS.
 3. TOILET ROOMS.
 4. STORAGE CLOSETS.
 5. SURGICAL ROOMS.
  
 END OF COMMENTS, QUESTIONS 561-805-6692