Plan Review Notes
Plan Review Notes For Permit 06020814
Permit Number 06020814
Review Stop E
Sequence Number 3
Notes
Date Text
2006-10-15 11:10:34*** UNSAT 3RD REVIEW ***
  
 1)NOTE: PLEASE SEE RESPONSE MENTIONS THE NEW AND
 UPDATED ENERGY CALCULATIONS WERE DONE, SIGNED, DATED
 AND SEALED, HOWEVER THE ONLY TWO SETS OF ENERGY
 CALCULATIONS SUBMITTED WERE THE SAME ONES FROM THE
 PREVIOUS REVIEW DATED 6/5/06.
 AS REQUESTED ON PREVIOUS REVIEW PLEASE SUBMIT AND
 ADJUSTAS NOTED IN PREVIOUS REVIEW NOTES.
 FBC 2004 CHAPTER 13 .
  
 ** ADDRESS IN SYSTEM HAS BEEN CORRECTED TO 850
 BELVEDERE RD PER THE ADDRESSING REVIEWER'S REQUEST
 WHICH IS AN EXTENSION OF RTHE PCN FOR 2700 PARKER AVE.
 THE PCN #'S ON ALL APPLICATIONS HAVE BEEN CHANGED TO
 74434333130020010.
  
 ** FYI , THE NOTICE OF COMMENCMENT SUBMITTED HAS SINCE
 EXPIRED AND HAS BEEOME "VOID". PLEASE SEE FS 713.13(2),
 WHEN THE WORK HAS NOT COMMENCED WITHIN 90DAYS OF
 RECORDING SUCH NOC, THE NOC BECOMES INVALID AND MUST BE
 RE-RECORDED.
 ** PLEASE KNOW, THIS RECORDED NOC ONLY NEEDS TO BE
 SUBMITTED ONCE PERMIT IS ISSUED AND READY FOR PICK UP.
  
 ** FYI, PLEASE KNOW, THE NEW PERMIT APPLICATION FOR THE
 CHANGE OF CONTRACTOR NOW HAS ALL THE SUB CONTRACTORS
 SIGNED ON. THESE HAVE BEEN CROSSED OUT AS THEY WERE NOT
 SIGNED ON ORIGINAL APPLICAITON AND WILL BE REQUIRED TO
 PULL SEPARATE SUB PERMITS ONCE PERMIT IS ISSUED. THIS
 WOULD BE THE $50 SUB PERMIT FEE FOR MOST , HOWEVER A
 SEPARATE PERMIT FOR LV AND SECURITY WILL BE REQUIRED
 AND SHALL BE BASED ON THEIR CONTACT/SCOPE OF WORK
 VALUE.
  
  
 IF THERE ARE ANY QUESTIONS, PLEASE DO NOT HESITATE IN
 CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]