Plan Review Notes
Plan Review Notes For Permit 06020814
Permit Number 06020814
Review Stop M
Sequence Number 2
Notes
Date Text
2006-08-07 00:00:00DENIED:
 FIRST PLAN REVIEW BY HAROLD MOSER
 4-3-06, ALL COMMENTS ADDRESSED.
  
 1.PLAN SHEET M-2 VENTILATION
 CALCULATION REFERS TO ASHRAE 62-89 THIS
 SHOULD READ ASHRAE 62-01.
  
 2.PLAN SHEET M-2 OCCUPANCY
 CLASSIFICATION PLAN INDICATES
 COMMERCIAL, THIS SHOULD READ BUSINESS
 ACCORDING TO 2004 FBC 304.1.
  
 3.PLAN SHEET M-2 MECHANICAL NOTE #4
 INDICATES DUCT SMOKE DETECTOR FOR FAN
 SHUTDOWN.PLEASE NOTE, FAN SHUTDOWN
 SHALL ALSO COMPLY WITH 606.4.1 THE DUCT
 SMOKE DETECTOR SHALL ACTIVATE A VISIBLE
 & AUDIBLE SUPERVISORY SIGNAL AT A
 CONSTANTLY ATTENDED LOCATION OR COMPLY
 WITH EXCEPTION 1 OR 2.
  
 PLANS DO NOT INDICATE IF THE VAULT HAS A
 FIRE RESISTANCE RATING.PLEASE CLARIFY.
 SHOULD CEILING TO THE VAULT BE RATED A
 CEILING DAMPER WILL BE REQUIRED.
  