2006-06-24 00:00:00 | *** UNSAT 2ND REVIEW *** |
| |
| ** PLEASE SSE SOME COMMENTS FROM |
| PREVIOUS REVIEW AND SEE ALSO NEW NOTE |
| NOT ON PREVIOUS REVIEW. |
| |
| 1) NOTE: PLEASE SEE TITLE BLOCKS ON |
| PLANS SHALL CONTAIN THE ADDRESS OF |
| BUILDING/SITE. PLEASE SEE THE RESPONSE |
| MENTIONS THIS WAS ADDED TO NORTH |
| ELEVATION, HOWEVER THIS IS REQUIRED ON |
| ALL SHEETS AND FOR ALL TRADES. |
| 61G1-16.004,61G15-23.002 |
| PREVIOUS REVIEW. |
| |
| 2) NOTE: PLEASE SEE SHEETS SIGNED AND |
| SEALED BY KILDAY AND ASSOCIATES AND |
| NEIL, SMITH AND ASSC. |
| PLEASE SEE MISSING REQUIRED INFORMATION |
| ON TITLE BLOCKS AS MENTIONED ON PREVIOUS |
| REVIEW. |
| THESE ARE MISSING THE PRINTED NAME AND |
| LICENSE NUMBERS, AND CERTIFICATE OF |
| AUTHORIZATION #S' . |
| PLEASE KNOW, NEIL AND ASSC IS MISSING |
| THE CA# AND KILDAY AND ASSC IS MISSING |
| PRINTED NAME, AND CA #. |
| 61G1-16.004, FS 481.219 |
| |
| 3) NOTE: PLEASE SEE THAT NO WIND LOAD |
| CALCULATIONS SIGNED, DATED AND SEALED |
| WERE SUBMITTED FOR LT POLE/SITE LTS. |
| PREVIOUS REVIEW |
| |
| ** NEW NOTE** |
| |
| 4) NOTE: PLEASE SEE ENERGY CALCULATIONS |
| ARE REQUIRED TO BE SIGNED, DATED AND |
| SEALED BY THE RESPONSIBLE DESIGNER(S). |
| PLEASE KNOW, AS SUBMITTED THESE DO NOT |
| SEEM TO COMPLY TO 2004 FBC CHAPTER 13, |
| AS CALC SHEETSDO NOT SEEM TO INDICATE |
| ALL LIGHTING AND AMOUNTS PERMITTED AND |
| USED PER 13-415.1.AB.1 FOR MIN |
| CALCULATIONS TO BE SHOWN, PLEASE ALSO |
| SEE LIGHTING DENSITIES REQUIRED IN |
| CALCULATIONS, 13-415.2.ABC.1 , ONLY ONE |
| OF THE TWO METHODS ARE PERMITTED. |
| PLEASE SEE TABLES. |
| |
| ** PLEASE SEE BUIIDING REVIEW COMMENTS |
| AS PRODUCT APPROVALS SHOULD NOT BE |
| ATTACHED TO PLANS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |