Plan Review Notes
Plan Review Notes For Permit 06020814
Permit Number 06020814
Review Stop P
Sequence Number 1
Notes
Date Text
2006-05-06 00:00:00PAUL SCHMITZ
 [email protected]
 FBC 2004 PLUMBING CODE PLAN REVIEW
 FBC2004 FUEL GAS CODEPLAN REVIEW
 FBC 2004 CH 11, FL ACESSIBILITY CODE
 AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPT.1, ADMINISTRATION, 2004 EDITION
  
 UNSAT
 1) SHTA-17 DETAIL 5/17 LOUNGE112
 11-4.24 SINKS.
 11-4.24.1 GENERAL.
 SINKS REQUIRED TO BE ACCESSIBLE BY
 SECTION 11-4.1 SHALL COMPLY WITH SECTION
 11-4.24.
 11-4.24.2 HEIGHT.
 SINKS SHALL BE MOUNTED WITH THE COUNTER
 OR RIM NO HIGHER THAN 34 INCHES (865 MM)
 ABOVE THE FINISH FLOOR.
 11-4.24.3 KNEE CLEARANCE.
 KNEE CLEARANCE THAT IS AT LEAST 27
 INCHES (685 MM) HIGH, 30 INCHES (760 MM)
 WIDE, AND 19 INCHES (485 MM) DEEP SHALL
 BE PROVIDED UNDERNEATH SINKS.
 11-4.24.4 DEPTH.
 EACH SINK SHALL BE A MAXIMUM OF 6?
 INCHES (165 MM) DEEP.
 11-4.24.5 CLEAR FLOOR SPACE.
 A CLEAR FLOOR SPACE AT LEAST 30 INCHES
 BY 48 INCHES (760 MM BY 1219 MM)
 COMPLYING WITH SECTION 11-4.2.4 SHALL BE
 PROVIDED IN FRONT OF A SINK TO ALLOW
 FORWARD APPROACH. ( NO DOORS )THE CLEAR
 FLOOR SPACE
 SHALL BE ON AN ACCESSIBLE ROUTE AND
 SHALL EXTEND A MAXIMUM OF 19 INCHES (485
 MM) UNDERNEATH THE SINK (SEE FIGURE
 11-32).
 11-4.24.6 EXPOSED PIPES AND SURFACES.
 HOT WATER AND DRAIN PIPES EXPOSED UNDER
 SINKS SHALL BE INSULATED OR OTHERWISE
 CONFIGURED SO AS TO PROTECT AGAINST
 CONTACT. THERE SHALL BE NO SHARP OR
 ABRASIVE SURFACES UNDER SINKS.
 11-4.24.7 FAUCETS.
 FAUCETS SHALL COMPLY WITH SECTION
 11-4.27.4. LEVER-OPERATED, PUSH-TYPE,
 TOUCH-TYPE, OR ELECTRONICALLY CONTROLLED
 MECHANISMS ARE ACCEPTABLE DESIGNS.
  
 2)SHT A-17 DETAIL 3/17 TOILET RM PLAN
 DRINKING FOUNTAIN
 11-4.15.5 CLEARANCES.
 (1) WALL- AND POST-MOUNTED CANTILEVERED
 UNITS SHALL HAVE A CLEAR KNEE SPACE
 BETWEEN THE BOTTOM OF THE APRON AND THE
 FLOOR OR GROUND AT LEAST 27 INCHES (685
 MM) HIGH, 30 INCHES (760 MM) WIDE, AND
 17 INCHES TO 19 INCHES (430 MM TO 485
 MM) DEEP [SEE FIGURE 11-27(A) AND FIGURE
 11-27(B)]. SUCH UNITS SHALL ALSO HAVE A
 MINIMUM CLEAR FLOOR SPACE 30 INCHES BY
 48 INCHES (760 MM BY 1219 MM) TO ALLOW A
 PERSON IN A WHEELCHAIR TO APPROACH THE
 UNIT FACING FORWARD.
  
 3)SHT A-9 ROOF DRAINS SEC 1101.1 SCOPE.
 THE PROVISIONS OF THIS CHAPTER SHALL
 GOVERN THE MATERIALS, DESIGN,
 CONSTRUCTION AND INSTALLATION OF STORM
 DRAINAGE.
 1101.2 WHERE REQUIRED.
 ALL ROOFS, PAVED AREAS, YARDS, COURTS
 AND COURTYARDS SHALL DRAIN INTO A
 SEPARATE STORM SEWER SYSTEM, OR A
 COMBINED SEWER SYSTEM, OR TO AN APPROVED
 PLACE OF DISPOSAL.
  
 4) 1106.2 VERTICAL CONDUCTORS AND
 LEADERS.
 VERTICAL CONDUCTORS AND LEADERS SHALL BE
 SIZED FOR THE MAXIMUM PROJECTED ROOF
 AREA, IN ACCORDANCE WITH TABLE 1106.2.
  
 5)DHT P-1 WATER HEATER
 607.3 THERMAL EXPANSION CONTROL.
 A MEANS OF CONTROLLING INCREASED
 PRESSURE CAUSED BY THERMAL EXPANSION
 SHALL BE PROVIDED WHERE REQUIRED IN
 ACCORDANCE WITH SECTIONS 607.3.1 AND
 607.3.2.
 CHECK VALVE.
 WHERE A BACKFLOW PREVENTION DEVICE,
 CHECK VALVE OR OTHER DEVICE IS INSTALLED
 ON A WATER SUPPLY SYSTEM UTILIZING
 STORAGE WATER HEATING EQUIPMENT SUCH
 THAT THERMAL EXPANSION CAUSES AN
 INCREASE IN PRESSURE, A DEVICE FOR
 CONTROLLING PRESSURE SHALL BE INSTALLED.
  
 6) 604.9 WATER HAMMER.
 THE FLOW VELOCITY OF THE WATER
 DISTRIBUTION SYSTEM SHALL BE CONTROLLED
 TO REDUCE THE POSSIBILITY OF WATER
 HAMMER. A WATER-HAMMER ARRESTOR SHALL BE
 INSTALLED WHERE QUICK-CLOSING VALVES ARE
 UTILIZED. WATER-HAMMER ARRESTORS SHALL
 BE INSTALLED IN ACCORDANCE WITH THE
 MANUFACTURER?S SPECIFICATIONS.TO BE
 INSTALLED BETWEEN THE LAST TWO FIXTURES,
 NOT IN THE CEILING.
  
 7) MATERIALS: SPECIFI THE TYPE AND
 SCHEDUE OF MATERIAL FOR THE WATER AND
 DRAINAGE PIPING.
  
 END OF COMMENTS, QUESTIONS 561-805-6692
  
  
  
  
  