Plan Review Notes For Permit 06020814 |
Permit Number |
06020814 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-04-03 00:00:00 | PLAN DENIED | | 1) PLEASE REFER TO SECTION 302.1.1 2004 | | FBC INCIDENTAL USE AREAS, AND TABLE | | 302.1.1 REFRIGERAN MACHINERY ROOM 2004 | | FBC. | | 2) PLEASE REFER TO SECTION 307.2.3 | | AUXILIARY AND SECONDARY DRAIN SYSTEM. | | 2004 FBC(M) | | 3) PLEASE PROVIDE DUCT SIZE FOR BATH | | ROOM EXHAUST ON PLANS.ROOM 114,115. | | 4) PLEASE PROVIDE EXHAUST DUCT SIZE FOR | | ROOM 104 ON PLANS | | 5) PLEASE REFER TO SECTION 601.4 | | BALANCED RETURN AIR 2004 FBC(M). | | 6) PLEASE SIZE RETURN AIR DUCT OM PLANS | | ROOMS 120,101,116. | | PLAN REVIEW BY HAROLD MOSER 561-805-6732 |
|