2006-05-10 00:00:00 | ******DENIED****** |
| |
| 1) PLEASE SEE COMMENTS REGARDING CORRECT |
| ADDRESSING OF BUILDING. ADDRESS SHALL BE |
| MINIMUM OF 6" IN HEIGHT AND CONTRASTING |
| TO BACKGROUND. PLEASE ADD NOTE TO |
| ELEVATIONS. |
| |
| 2) LIFE SAFETY NFPA 101, 2003 EDITION |
| SHALL BE REFERENCED. |
| |
| 3) PLEASE PROVIDE CLARIFICATION |
| REGARDING TRAVEL DISTANCE. IS THIS NOTE |
| REFERENCING TRAVEL DISTANCE TO EXITS OR |
| COMMON PATH OF TRAVEL? NFPA 101, |
| SECTIONS 38.2.5 AND 38.2.6. |
| |
| 4) PLEASE INDICATE THE MINIMUM INTERIOR |
| FINISH CLASSIFICATION FOR WALLS AND |
| CEILINGS IN TERMS OF CLASS A,B OR C. |
| |
| 5) SHT M-2 MENTIONS A FIRE ALARM SYSTEM. |
| (NOTE #4) DUCT SMOKE DETECTORS SHALL |
| INITIATE A GENERAL FIRE ALARM IN |
| ACCORDANCE WITH LOCAL REQUIREMENTS. |
| WHERE NO FIRE ALARM IS PROVIDED, |
| AUDIBLE/VISUAL DEVICES ARE STILL |
| REQUIRED FOR OCCUPANT NOTIFICATION. |
| |
| 6) SEPARATE SHOP DRAWINGS AND PERMIT |
| REQUIRED FOR FIRE ALARM SYSTEM. |
| |
| 7) PLEASE CLARIFY NOTE ON SHT E-5 IN |
| REFERENCE TO MONITORING OF SMOKE |
| DETECTORS. |
| |
| |
| MIKE WENNERGREN, CAPTAIN/WPBFR |
| FIRE PLAN REVIEW (561) 805-6722 |