2006-03-20 00:00:00 | ***** UNSAT ****** |
| |
| 1)NOTE: PLEASE SEE COMMENTS WITH RESPECT |
| TO ADRESSING OF PROJECT. PLEASE BE SURE |
| TO ADD ADDRESS OF LOCATION TO PLANS WHEN |
| FINAL ADDRESS IS CONFIRMED BEFORE |
| RESUBMITTING PLANS. |
| FAC 61G1-16.004 |
| |
| 2)NOTE: PLEASE SEE WIND LOADS ARE |
| REQUIRED AT THIS TIME FOR REVIEW BY THE |
| STRUCTURAL REVIEWER. THESE SHOULD |
| INCLUDE POLES W/ FIXTIURES. |
| |
| 3)NOTE: PLEASE SEE MISSING CERTIFICATE |
| OF AUTHORIZATION NUMBER ON LANDSCAPE |
| PLANS. |
| FAC 61G1-16.004, FS 481.0219 |
| ** PLEASE KNOW, THIS IS NOT FOR JLRD. |
| |
| 4) NOTE: PLEASE BE SURE PLANS REFERENCE |
| THE CURRENT CODE AS FOLLOWS. |
| 2002 NFPA-70(NEC), 2003 NFPA-101, 2002 |
| NFPA-70 |
| |
| 5)NOTE: PLEASE CLARIFY WHAT MEANS IS |
| GOING TO BE PROVIDED FOR CONNECTION OF |
| PORTABLE GENERATOR ? (IF ANY) WILL THERE |
| BE A RECEPT? |
| 215.5 |
| |
| 6)NOTE: PLEASE SEE MISSING FOOTER STEEL |
| AS PART OF THE GROUNDING ELECTRODE |
| SYSTEM.250.50, 250.52 |
| |
| 7)NOTE: PLEASE SEE RISER IS SHOWING AN |
| "EUIPMENT GROUNDING CONDUCTOR" TO THE |
| FIRST MEANS OF DISCONNECT FROM FPL |
| TRANSFORMER? THIS APPEARS TO BE A |
| MISPRINT.? |
| PLEASE SEE 250.6,250.24B, THE "EQUIPMENT |
| GROUNDING CONDUCTOR" IS ONLY INSTALLED |
| AFTER THE FIRST MEANS OF DISCONNECT. |
| |
| ** PLEASE BE SURE TO SEE ANY OTHER |
| POSSIBLE COMMENTS FROM OTHER TRADES |
| WHICH MAY AFFECT ELECTRICAL PLANS. |
| |
| ** PLEASE COMPLETELY REMOVE ANY |
| OLD/VOIDED SHEETS FROM SETS. ONLY INSERT |
| THE NEW REVISED SHEETS INTO SETS. ONE |
| COPY OF THE OLD/VOIDED REMOVED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| |
| PLEASE SUBMIT THE ABOVE FOR REVIEW. IF |
| THERE ARE ANY QUESTIONS, PLEASE DO NOT |
| HESITATE IN CONTACTING THIS OFFICE. |
| |