2006-05-05 00:00:00 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| |
| FBCFLORIDA BUILDING CODE 2004 |
| FBC EBFLORIDA BUILDING CODE 2004 |
| EXISTING BUILDING CODE |
| FBC*CITY OF WEST PALM BEACH |
| AMENDMENTS TO THE FBC2004 |
| |
| 1.)A NOTICE OF COMMENCEMENT MUST BE |
| FILED WITH THE CLERK OF COURTS BEFORE A |
| PERMIT CAN BE ISSUED, FS713.13. |
| |
| 2.)IMPACT FEES MUST BE PAID TO PALM |
| BEACH COUNTY.THE PLANS MUST BE STAMPED |
| AND THE RECEIPT ATTACHED TO THE |
| APPLICATION.561-233-5025 FOR MORE |
| INFORMATION. |
| |
| 3.)PROVIDE A SURVEY FOR THIS PROPERTY, |
| FBC*106.3.4.IF THE IMPROVEMENT CROSSES |
| A PROPERTY LINE, A UNITY OF TITLE WILL |
| BE REQUIRED.THE RECORDED UNITY OF |
| TITLE MUST BE PROVIDED PRIOR TO PERMIT |
| ISSUANCE. |
| |
| 4.)THE CONTRACTOR'S INSURANCE IS |
| EXPIRED.PLEASE PROVIDE A CURRENT |
| INSURANCE CERTIFICATE PRIOR TO PERMIT |
| ISSUANCE. |
| |
| 5.)PROVIDE PRODUCT APPROVALS FOR THE |
| COMPONENTS AND CLADDING.PRODUCT |
| APPROVALS ARE TO BE REVIEWED BY THE |
| DESIGNER OF RECORD, FBC*106.3.3. |
| PROVIDE FOR ALL COMPONENTS AND CLADDING, |
| INCLUDING |
| |
| IMPACT STOREFRONT |
| HOLLOW METAL DOORS |
| BULLET RESISTANT VISION WINDOW |
| TILE ROOF, CIRCLE METHOD OF ATTACHMENT |
| ON THE PRODUCT APPROVAL |
| |
| 6.)THE PLANS SHOW IMPACT GLASS.IF |
| THIS IS CHANGED ON THE PLAN TO NON |
| IMPACT WITH REMOVABLE SHUTTERS, BE |
| ADVISED THAT USE OF REMOVABLE SHUTTERS |
| ON COMMERCIAL BUILDINGS MUST BE APPROVED |
| BY THE BUILDING OFFICIAL.IF THERE IS A |
| CHANGE TO THE PLANS IN REGARDS TO IMPACT |
| PROTECTION, FAILURE TO SUBMIT A |
| HURRICANE SHUTTER INSTALLATION PLAN WILL |
| CAUSE DELAYS IN PERMIT ISSUANCE.THIS |
| ITEM IS INFORMATIONAL ONLY. |
| |
| 7.)INFORMATIONAL ONLY; SEPARATE |
| PERMITS WILL BE REQUIRED FOR THE SCREEN |
| WALL AND THE DUMPSTER ENCLOSURE. |
| COMPLETE A PERMIT APPLICATION FOR THE |
| DUMPSTER ENCLOSURE AND PROVIDE WITH THE |
| RESUBMITTAL.SEPARATE PLANS ARE NOT |
| NECESSARY. |
| |
| 8.)THE CERTIFICATE OF AUTHORIZATION |
| NUMBER FOR SOUTHERN DESIGN GROUP INC. IS |
| REQUIRED TO BE ON EACH SHEET, |
| FAC61G15-23.002. |
| |
| 9.)THE PARKING STRIPING IS TO COMPLY |
| WITH THE CITY OF WEST PALM BEACH |
| STANDARD, SEE ATTACHED DETAIL. |
| |
| 10.)DECLARE THE MEAN ROOF HEIGHT SO |
| THAT MOMENTS OF RESISTANCE FOR THE ROOF |
| TILE CAN BE DETERMINED. |
| |
| 11.)PROVIDE THE DISTANCE BETWEEN THE |
| PROPOSED BANK AND THE EXISTING BUILDING, |
| FBC TABLE 602.IF THEY ARE ON THE SAME |
| LOT, SHOW THE ASSUMED PROPERTY LINE AND |
| COMPLIANCE WITH TABLE 602. |
| |
| 12.)THE PROPERTY LINE IS NOT CLEAR ON |
| THE SITE PLAN.IF THE SCREEN WALL 7-SP4 |
| IS ALONG A PROPERTY LINE, SHOW THE |
| PROPERTY LINE ON THE DETAIL.THE FOOTER |
| CANNOT ENCROACH THE PROPERTY LINE.SEE |
| SP1.SOME OF THE TEXT IS UPSIDE DOWN OR |
| IN THE WRONG LOCATIONS.THERE IS A LINE |
| SHOWING ?PROPOSED LEASE LINE? WHICH |
| SEEMS TO INDICATE ONLY ONE PARCEL.A |
| BOUNDARY SURVEY SHOULD HELP TO CLARIFY |
| LOT LINES. |
| |
| 13.)A1 STATES THAT THERE IS A 75' MAX |
| TRAVEL DISTANCE.DO YOU MEAN COMMON |
| PATH OF TRAVEL FBC1013.3?THE TRAVEL |
| DISTANCE EXCEEDS 75'.IF YOUR DESIGN |
| INTENTION IS TO EXCEED CODE AND RESTRICT |
| MAXIMUM TRAVEL DISTANCE TO 75' PLEASE |
| REVISE THE PLANS.OTHERWISE REVISE THE |
| 75' MAX TRAVEL DISTANCE REQUIREMENT |
| FBC1015.1.NOTE THAT ONLY ONE EXIT IS |
| REQUIRED FBC1014.1 SO THERE IS NO |
| REQUIREMENT FOR COMMON PATH OF TRAVEL. |
| IT IS ACCEPTABLE TO EXCEED CODE BUT THE |
| PLANS SHOULD BE CONSISTENT WITH YOUR |
| DESIGN SPECIFICATION. |
| |
| 14.)SHOW THE MANEUVERING CLEARANCE, |
| PULL SIDE, FOR DOORS 104, 108, 112, |
| FIGURE FBC 11-25, FBC11-4.13.6. |
| |
| 15.)BREAK ROOM SINK IS TO COMPLY WITH |
| FBC11-4.24.SHOW ALL DIMENSIONS, |
| INCLUDING KNEE CLEARANCE. |
| |
| 16.)THE TELLER COUNTER IS SHOWN AS |
| 40IN.SEE FBC11-7.2(2) AND SHOW |
| COMPLIANCE ON THE PLAN. |
| |
| 17.)S1 SHOWS DISTANCES OF 29FT (EAST |
| WALL) AND 16FT (SOUTH WALL) BETWEEN |
| GROUT FILLED CELLS.A 4FT DISTANCE IS |
| MORE TYPICAL FOR CBS CONSTRUCTION.IF |
| THIS IS AN ERROR, PLEASE REVISE THE |
| PLANS.IF THIS IS NOT AN ERROR, PLEASE |
| CONTACT ME TO DISCUSS. |
| |
| 18.)SIGN THE OWNER/AGENT LINE OF THE |
| ENERGY CALC, FBC13-103.1. |
| |
| 19.)THE SQUARE FOOT AREA ON THE ENERGY |
| CALCS IS 3250, THE PLAN IS 3594.THE |
| TWO SHOULD BE CONSISTENT. |