2006-05-18 00:00:00 | |
| |
| DENIED |
| |
| 61G15-23.002 SEAL, SIGNATURE AND DATE |
| SHALL BE AFFIXED. |
| (1) A PROFESSIONAL ENGINEER SHALL SIGN |
| HIS NAME AND AFFIX HIS SEAL TO ALL |
| PLANS, SPECIFICATIONS, REPORTS, FINAL |
| BID DOCUMENTS PROVIDED TO THE OWNER OR |
| THE OWNER?S REPRESENTATIVE, OR OTHER |
| DOCUMENTS PREPARED OR ISSUED BY SAID |
| REGISTRANT AND BEING FILED FOR PUBLIC |
| RECORD. THE DATE THAT THE SIGNATURE AND |
| SEAL IS AFFIXED AS PROVIDED HEREIN SHALL |
| BE ENTERED ON SAID PLANS, |
| SPECIFICATIONS, REPORTS, OR OTHER |
| DOCUMENTS IMMEDIATELY UNDER THE |
| SIGNATURE OF THE PROFESSIONAL ENGINEER. |
| (2) EACH SHEET OF PLANS AND PRINTS |
| WHICH MUST BE SEALED UNDER THE |
| PROVISIONS OF CHAPTER 471, F.S., SHALL |
| BE SEALED, SIGNED AND DATED BY THE |
| PROFESSIONAL ENGINEER IN RESPONSIBLE |
| CHARGE. ENGINEERS SHALL LEGIBLY INDICATE |
| THEIR NAME, ADDRESS, AND LICENSE NUMBER |
| ON EACH SHEET. IF PRACTICING THROUGH A |
| DULY AUTHORIZED ENGINEERING BUSINESS, |
| ENGINEERS SHALL LEGIBLY INDICATE THEIR |
| NAME AND LICENSE |
| NUMBER, AS WELL AS, THE NAME, ADDRESS, |
| AND CERTIFICATE OF AUTHORIZATION NUMBER |
| OF THE ENGINEERING BUSINESS ON EACH |
| SHEET. |
| |
| 2) SEE FBC. TABLE 2304.9.1 FOR THE |
| MINIMUM REQUIREMENTS FOR THE FASTENER |
| SPACING FOR ROOF SHEETING. |
| |
| 3) NOTE: NO FASTENERS SHALL BE SPACED |
| FARTHER THAN INDICATED ON THE NOA. |
| ENHANCEMENT SHALL BE DONE FOR ZONES 2 |
| AND 3 ONLY. |
| |
| 4) RAS117 10.4.5 ALL FRACTIONS ARE TO BE |
| ROUNDED DOWN TO THE NEXT WHOLE NUMBER. |
| |
| 5) PLEASE LOOK CLOSELY AT RAS117 AND |
| FOLLOW THE EXAMPLE WHEN DETERMINING THE |
| CALCULATIONS FOR FASTENER SPACING. |
| |
| 6) SEE COMMENT #1 IN REGARDS TO |
| SIGNATURES. PHOTOCOPIES AND INITIALS ARE |
| NOT ACCEPTABLE |
| |
| MYRON JACOBS |
| BUILDING PLAN REVIEWER |
| TEL:(561)805-6726 |
| |
| |