2006-03-03 00:00:00 | DENIED |
| REFERENCE: FBC-2004 R4101 SWIMMING POOLS |
| |
| PLEASE ADJUST YOUR NOTES, DETAILS, OR |
| SUBMITTALS TO REFLECT THE FOLLOWING |
| INFORMATIOM REQUIRED FOR PLAN REVIEW. |
| |
| 1) COMPLY WITH FBC-2004 SEC. R4101 |
| PRIVATE SWIMMING POOLS.(ADD TO NOTES) |
| 2) FBC-2004 R4101.6.6.3 ENTRAPMENT AD- |
| VOINANCE PLEASE SUBMIT AN 1-1/2" ATMOS- |
| PHERIC VENT LENGTH CHART WITH PUMP SIZE |
| AND TOTAL LENGTH OF VENT TO COMPLY WITH |
| 3 SECOND RELEASE. |
| 3) FBC-2004 R4101.6.6.5 WHERE PROVIDED, |
| THE VACUUM OR PRESSURE CLEANER FITTING |
| SHALL BE LOCATED AT LEAST 6" AND NOT |
| GREATER THAN 12" BELOW THE MINIMUM OPER- |
| ATING WATER LEVEL OR AS AN ATTACHMENT TO |
| THE SKIMMER.(DETAILS NEEDED) |
| 4) FBC-2004 R4101.12.1 |
| PRESSURE TESTS. PER MANUFACTURE |
| RECOMMENDATIONS, NO AIR TEST SHALL BE |
| APPROVED FOR PVC PIPE AND FITTINGS. (ADD |
| TO NOTES) |
| 5) FBC-2004 4101.14.1 SWIMMING POOL |
| WATER HEATERS SHALL BEAR THE LABEL OF A |
| RECOGNIZED TESTING AGENCY. MANUFACTURE |
| SHEETS REQUIRED. (SUBMITTAL REQUIRED) |
| 6) FBC-2004 R4101.14.2 WATER RETENTION, |
| PROVIDE A POSITIVE MEANS OF RETAINING |
| WATER IN HEATER WHEN PUMP IS SHUT OFF. |
| (MANUFACTURE CUT SHEETS REQUIRED) |
| |
| END OF COMMENTS: |
| |