Plan Review Notes
Plan Review Notes For Permit 06020769
Permit Number 06020769
Review Stop P
Sequence Number 1
Notes
Date Text
2006-03-03 00:00:00DENIED
 REFERENCE: FBC-2004 R4101 SWIMMING POOLS
  
 PLEASE ADJUST YOUR NOTES, DETAILS, OR
 SUBMITTALS TO REFLECT THE FOLLOWING
 INFORMATIOM REQUIRED FOR PLAN REVIEW.
  
 1) COMPLY WITH FBC-2004 SEC. R4101
 PRIVATE SWIMMING POOLS.(ADD TO NOTES)
 2) FBC-2004 R4101.6.6.3 ENTRAPMENT AD-
 VOINANCE PLEASE SUBMIT AN 1-1/2" ATMOS-
 PHERIC VENT LENGTH CHART WITH PUMP SIZE
 AND TOTAL LENGTH OF VENT TO COMPLY WITH
 3 SECOND RELEASE.
 3) FBC-2004 R4101.6.6.5 WHERE PROVIDED,
 THE VACUUM OR PRESSURE CLEANER FITTING
 SHALL BE LOCATED AT LEAST 6" AND NOT
 GREATER THAN 12" BELOW THE MINIMUM OPER-
 ATING WATER LEVEL OR AS AN ATTACHMENT TO
 THE SKIMMER.(DETAILS NEEDED)
 4) FBC-2004 R4101.12.1
 PRESSURE TESTS. PER MANUFACTURE
 RECOMMENDATIONS, NO AIR TEST SHALL BE
 APPROVED FOR PVC PIPE AND FITTINGS. (ADD
 TO NOTES)
 5) FBC-2004 4101.14.1 SWIMMING POOL
 WATER HEATERS SHALL BEAR THE LABEL OF A
 RECOGNIZED TESTING AGENCY. MANUFACTURE
 SHEETS REQUIRED. (SUBMITTAL REQUIRED)
 6) FBC-2004 R4101.14.2 WATER RETENTION,
 PROVIDE A POSITIVE MEANS OF RETAINING
 WATER IN HEATER WHEN PUMP IS SHUT OFF.
 (MANUFACTURE CUT SHEETS REQUIRED)
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561)805-6730
 FAX(561)805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561)805-6721
  