Plan Review Notes
Plan Review Notes For Permit 06020766
Permit Number 06020766
Review Stop P
Sequence Number 1
Notes
Date Text
2006-03-10 00:00:00DENIED
 REFERENCE:FBC-2004 R4101 SWIMMING POOLS
  
 PLEASE ADJUST YOUR NOTES, DETAILS, OR
 SUBMITTALS TO REFLECT THE FOLLOWING
 INFORMATION REQUIRED FOR PLAN REVIEW.
  
 1. COMPLY WITH FBC-2004 SEC. 4101
 PRIVATE SWIMMING POOLS. (ADD TO NOTES)
 2. FBC-2004 SEC. R4101.6.6 ENTRAPMENT
 PROTECTION FOR SUCTION INLETS. NEED EN-
 GINEERED TABLE FOR "VENT PIPE MAXIMUM
 LENGTH" INDICATING PUMP SIZES, AVERAGE
 FLOW (GPM), AND MAXIMUM LENGTH OF 1-1/2"
 PVC VENT PIPE TO COMPLY WITH THREE
 SECOND RELEASE.
 3. FBC-2004 R4101.6.6.5 PROVIDE DETAIL
 OF APPROVED VACUUM OR CLEANER FITTING
 WITH MODEL NUMBER.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561)80506730
 FAX (561)805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561)805-6721