Plan Review Notes For Permit 06020766 |
Permit Number |
06020766 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-03-10 00:00:00 | DENIED | | REFERENCE:FBC-2004 R4101 SWIMMING POOLS | | | | PLEASE ADJUST YOUR NOTES, DETAILS, OR | | SUBMITTALS TO REFLECT THE FOLLOWING | | INFORMATION REQUIRED FOR PLAN REVIEW. | | | | 1. COMPLY WITH FBC-2004 SEC. 4101 | | PRIVATE SWIMMING POOLS. (ADD TO NOTES) | | 2. FBC-2004 SEC. R4101.6.6 ENTRAPMENT | | PROTECTION FOR SUCTION INLETS. NEED EN- | | GINEERED TABLE FOR "VENT PIPE MAXIMUM | | LENGTH" INDICATING PUMP SIZES, AVERAGE | | FLOW (GPM), AND MAXIMUM LENGTH OF 1-1/2" | | PVC VENT PIPE TO COMPLY WITH THREE | | SECOND RELEASE. | | 3. FBC-2004 R4101.6.6.5 PROVIDE DETAIL | | OF APPROVED VACUUM OR CLEANER FITTING | | WITH MODEL NUMBER. | | | | END OF COMMENTS: | | | | REVIEW BY MIKE PERSON | | (561)80506730 | | FAX (561)805-6731 | | E-MAIL [email protected] | | UNDER SUPERVISION OF K.STEVENS | | (561)805-6721 |
|