Plan Review Notes
Plan Review Notes For Permit 06020735
Permit Number 06020735
Review Stop E
Sequence Number 1
Notes
Date Text
2006-03-01 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE VALUE ON THE PERMIT APPLICATION
 MUST INCLUDE ALL ASSOCIATED EQUIPMENT
 AND LABOR PER FBC.
  
 2} 225.36 SUITABLE FOR SERVICE
 EQUIPMENT.
 THE DISCONNECTING MEANS SPECIFIED IN
 225.31 SHALL BE SUITABLE FOR USE AS
 SERVICE EQUIPMENT.
  
 3} 702-5. CAPACITY AND RATING
 AN OPTIONAL STANDBY SYSTEM SHALL HAVE
 ADEQUATE CAPACITY AND RATING FOR THE
 SUPPLY OF ALL EQUIPMENT INTENDED TO BE
 OPERATED AT ONE TIME. PROVIDE A
 CALCULATION AND INDICATING THE LOAD TO
 BE SERVED BY THE GENEERATOR.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  