Plan Review Notes For Permit 06020735 |
Permit Number |
06020735 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-03-01 00:00:00 | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIEW. | | | | 1} THE VALUE ON THE PERMIT APPLICATION | | MUST INCLUDE ALL ASSOCIATED EQUIPMENT | | AND LABOR PER FBC. | | | | 2} 225.36 SUITABLE FOR SERVICE | | EQUIPMENT. | | THE DISCONNECTING MEANS SPECIFIED IN | | 225.31 SHALL BE SUITABLE FOR USE AS | | SERVICE EQUIPMENT. | | | | 3} 702-5. CAPACITY AND RATING | | AN OPTIONAL STANDBY SYSTEM SHALL HAVE | | ADEQUATE CAPACITY AND RATING FOR THE | | SUPPLY OF ALL EQUIPMENT INTENDED TO BE | | OPERATED AT ONE TIME. PROVIDE A | | CALCULATION AND INDICATING THE LOAD TO | | BE SERVED BY THE GENEERATOR. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 | | |
|