Plan Review Notes
Plan Review Notes For Permit 06020711
Permit Number 06020711
Review Stop B
Sequence Number 1
Notes
Date Text
2006-02-15 00:00:001) THE PRODUCT APPROVALS SUBMITTED ARE
 NOT FOR RECOVER DECKS. WHAT WAS
 SUBMITTED IS FOR A MODIFIED BITUMEN ROOF
 SYSTEM,NOT RECOVER DECKS. HOWEVER, THE
 RECOVER SYSTEMS ARE FOR
 CONCRETE/STEEL/AND LIGHTWEIGHT CONCRETE.
 NO WOOD DECK IS MENTIONED IN THE PRODUCT
 APPROVAL. SEE THE NOA FOR ROOF RECOVER.
  
 2) AFTER A PRE-INSPECTION BY INSPECTOR
 CHUCK JORDAN, HE IS REQUESTING TO SEE
 THE DECKING DUE TO SOME AREA WHICH WERE
 QUESTIONABLE. ANY QUESTIONS CONCERNING
 THIS MATTER,PLEASE CONTACT MR.JORDAN AT
 #(561)805-6673.
  
 3) NOTE: IF FL#735-R1 IS SUBMITTED FOR
 REVIEW,GENERAL LIMITATION#7 REQUIRES THE
 CALCULATIONS TO BE PREPARED BY A FLORIDA
 REGISTERED PROFESSIONAL
 ENGINEER,ARCHITECT OR ROOFING
 CONSULTANT. READ GENERAL LIMITATION#7
 FOR MORE INFORMATION. ALSO GENERAL
 LIMITATION#9 CANNOT BE USED IF THE
 PRESSURES ARE BELOW -89PSF.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 TEL:(561)805-6726