Plan Review Notes
Plan Review Notes For Permit 06020706
Permit Number 06020706
Review Stop E
Sequence Number 1
Notes
Date Text
2006-02-23 00:00:00NEED TO SHOW BRANCH CIRCUIT NUMBERS FOR
 THE OUTLETS AND LIGHTS (NEW)
  
 PANEL SCHEDULE DOES NOT REFLECT LOADS
 SHOWN ON DRAWINGS. LIGHTS AND OUTLETS.
  
 NO LOW VOLTAGE SYSTEMS SHOWN NEW
 TELEPHONE COMPUTERS, ECT. ECT.
 NO ROUGH INSPECTION WITHOUT PLANS FOR
 LOW VOLTAGE.
  
 THERE IS NO SIGNATURE OF THE RESONSIBLE
 PARTY FOR THESE DRAWINGS.
  
 NEED TO SHOW THE LOCATION OF THE PANEL
 AND METER AND SERVICE.