Plan Review Notes
Plan Review Notes For Permit 06020706
Permit Number 06020706
Review Stop B
Sequence Number 1
Notes
Date Text
2006-03-06 00:00:00DENIED
  
 1) SPECIFY THE LOCATION OF FIRE OR
 FIRE/SMOKE RATED WALLS. SEE FBC 706.
  
 2) ONE HOUR FIRE TENANT SEPARATION IS
 REQUIRED FROM ADJACENT TENANTS. SPECIFY
 LOCATIONS WITH DASHED OR DOTTED LINES
 FOR CLARITY. SEE FBC 708.
  
 3) SPECIFY THE REQUIRED CLASS OF WALL
 AND CEILING FINISHES PER FBC 803.
  
 4) THE SINK AND CABINETS ARE REQUIRED TO
 COMPLY WITH ACCESSIBILITY REQUIREMENTS.
 SEE FBC 11-4.24 AND 11-4.32.4. PROVIDE
 ELEVATIONS.
  
 5)11-4.1.6(2) DUTY TO PROVIDE
 AN ACCESSIBLE PATH OF TRAVEL TO ALTERED
 AREAS SHALL BE DEEMED DISPROPORTIONATE
 TO THE OVERALL ALTERATION WHEN THE COST
 EXCEEDS 20 % OF THE COST OF THE ALTERA-
 TION TO THE PRIMARY FUNCTION AREA.
 (A)(I) AN ACCESSIBLE ENTRANCE
 (II) AN ACCESSIBLE ROUTE
 (III) AT LEAST ONE ACCESSIBLE REST-
 ROOM FOR EACH SEX OR A SINGLE
 UNISEX RESTROOM
 (IIII) ACCESSIBLE TELEPHONE
 (IV) ELEMENTS SUCH AS PARKING, STOR-
 AGE OR ALARMS.
 SUBMIT A COST BREAKDOWN SHOWING THE 20%
 OF ALTERATION COST TO BE SPENT ON
 ACCESSIBILITY.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved