Plan Review Notes
Plan Review Notes For Permit 06020693
Permit Number 06020693
Review Stop M
Sequence Number 3
Notes
Date Text
2006-08-02 00:00:00*** DENIED ***
 1) AS REQUESTED IN LAST TWO REVIEWS,
 SUPPLY AIR DUCT (FLEX) TO LIVING ROOM
 NEEDS TO BE SIZED.
  
 2) AS REQUESTED IN LAST TWO REVIEWS,
 SUPPLY AIR GRILL IN HALL (FOYER) NEEDS
 TO BE SIZED.
  
 3) SEE ATTACHED NOTICE FS 553.80(2)(B)
 FOUR TIMES THE FEE.
  
 4) SOME SUPPLY AIR DUCTS ARE SHOWING 2
 DIFFERENT SIZES FOR THEM (SEE HIGH
 LIGHTS ON MECHANICAL PLANS), PLEASE
 CORRECT.
  
 5) PLEASE EXPLAIN OR REMOVE 18"X30"
 SUPPLY AIR GRILL UNDER AIR HANDLER.
  
 6) PLEASE SUBMIT MANUAL D CALCULATIONS
 FOR RESIDENTIAL DUCT DESIGN, PER 2004
 FBC/R M1601.1 AND FBC 13-610.1.ABC.1,
 (AS MOST SUPPLY AIR DUCTS ARE SIZED AT
 9") (SEE ATTACHED MANUAL D COVER SHEET).
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.