2006-08-02 00:00:00 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} NOTE #1 REFERS TO "IAW" PLEASE NOTE
 THAT THE STATE OF FLORIDA HAS ADOPTED
 NFPA 70 OR THE NEC. IF REFERENCING
 ANOTHER CODE TO USE FOR WIRING
 COMPLIANCE, INDICATE WHERE IT IS
 REFERENCED AS REPLACING THE BUILDING
 CODE REFERENCES. ALSO PLEASE INFORM ME
 WHERE I CAN OBTAIN OR READ "IAW" CODES.
 OTHERWISE TAKE ALLREFERENCES TO SAME OFF
 THE DOCUMENTS.
  
 2} DUE TO THE METER LOCATION, A
 DISCONNECT IS REQUIRED PER 225.32.
 INDICATE LOCATION ON PLAN, AND ON THE
 RISER.
  
 3} CIRCUIT #14 NEEDS #12 WIRE IF A 20
 AMP BREAKER IS USED. 310.16.
  
 4} THE PANEL SCHEDULE INDICATES SEPARATE
 WASHER AND DRYER, THE PLAN HAS A
 COMBINATION UNIT, PLEASE CLARIFY.
  
 PLEASE SEE THAT THE APPLIANCE OUTLETS IN
 THE KITCHEN ARE NOT REQUIRED TO BE GFI,
 BUT MUST BE INSTALLED IF ON PLANS.
  
 5} RECEPTACLE SPACING MUST COMPLY WITH
 210.52(A) (1) AND 210.52(A)(2). SEE
 REVIEWED PLAN.
  
 6} BATH ROOMS MUST HAVE RECEPTALES PER
 210.52(D).
  