2006-08-02 00:00:00 | |
| |
| NONCOMPLIANT |
| |
| PLEASE MAKE THE FOLLOWING CORRECTIONS |
| FOR CODE COMPLIANCE AND RESUBMIT FOR |
| REVIEW. |
| |
| 1} NOTE #1 REFERS TO "IAW" PLEASE NOTE |
| THAT THE STATE OF FLORIDA HAS ADOPTED |
| NFPA 70 OR THE NEC. IF REFERENCING |
| ANOTHER CODE TO USE FOR WIRING |
| COMPLIANCE, INDICATE WHERE IT IS |
| REFERENCED AS REPLACING THE BUILDING |
| CODE REFERENCES. ALSO PLEASE INFORM ME |
| WHERE I CAN OBTAIN OR READ "IAW" CODES. |
| OTHERWISE TAKE ALLREFERENCES TO SAME OFF |
| THE DOCUMENTS. |
| |
| 2} DUE TO THE METER LOCATION, A |
| DISCONNECT IS REQUIRED PER 225.32. |
| INDICATE LOCATION ON PLAN, AND ON THE |
| RISER. |
| |
| 3} CIRCUIT #14 NEEDS #12 WIRE IF A 20 |
| AMP BREAKER IS USED. 310.16. |
| |
| 4} THE PANEL SCHEDULE INDICATES SEPARATE |
| WASHER AND DRYER, THE PLAN HAS A |
| COMBINATION UNIT, PLEASE CLARIFY. |
| |
| PLEASE SEE THAT THE APPLIANCE OUTLETS IN |
| THE KITCHEN ARE NOT REQUIRED TO BE GFI, |
| BUT MUST BE INSTALLED IF ON PLANS. |
| |
| 5} RECEPTACLE SPACING MUST COMPLY WITH |
| 210.52(A) (1) AND 210.52(A)(2). SEE |
| REVIEWED PLAN. |
| |
| 6} BATH ROOMS MUST HAVE RECEPTALES PER |
| 210.52(D). |
| |
| BILL TROBAUGH |
| ELECTRICAL PLAN REVIEW |