Plan Review Notes
Plan Review Notes For Permit 06020693
Permit Number 06020693
Review Stop B
Sequence Number 2
Notes
Date Text
2006-06-29 00:00:00BUILDING REVIEW 2ND CHECKLIST:
 1- WILL NEED RE-RECORDED NOTICE OF
 COMMENCEMENT. RECORDED NOC WILL EXPIRE
 BY 6-30-06 IF WORK IS NOT STARTED BY
 THEN. SEC. 713.13.9(2) FL. STATUTES.
  
 2- REVISE ORIGINAL DWGS. HAND WRITTEN
 REVISIONS ARE NOT ACCEPTABLE. PROVIDE
 BATHROOM WITH DOOR THAT ALLOWS 29" MIN.
 CLEAR OPENING.
 SECTION R322 2004 RESIDENTIAL CODE.
  
 3- SPECIFY ATTIC ACCESS AND LOCATION.
 NOTE: REVISE ORIGINAL DRAWING.
 SEC. R807 2004 RESIDENTIAL CODE.
  
 4- RULE 9B-72 OF DCA REQUIRES FLORIDA OR
 LOCAL PRODUCT APPROVAL FOR:
 A) PRECAST LINTELS. INFORMATION WAS
 NOT SUBMITTED AND BE AWARE THAT DADE
 COUNTY NOA #03-0605.05 IS EXPIRED. NEED
 TO PROVIDE CURRENT ONE.
 B) ALL STRUCTURAL CONNECTORS SPECIFIED
 ON PLANS. INFORMATION SUBMITTED IS NOT A
 PRODUCT APPROVAL REPORT. AND NEED
 PRODUCT APPROVAL FOR ALL CONNECTORS
 SPECIFIED ON PLANS. CHECK TRUSS ANCHOR
 SCHEDULE AND ALL DETAILS TO SEE WHICH
 CONNECTORS ARE SPECIFIED.
 C) ROOF SHINGLES. NOT SUBMITTED.
 D) SLIDING GLASS DOORS. PROVIDE DADE
 COUNTY NOA WITH CLEAR & LEGIBLE DWGS.
 ONE SUBMITTED IS NOT READABLE.
 E) ENTRY DOOR. ONE SUBMITTED IS FOR
 6'-8" HIGH DOORS. NEED FOR 8'-0" HIGH
 DOORS AS SPECIFIED ON PLANS. MAKE SURE
 PRINTS ARE CLEAR AND LEGIBLE.
 F) DOOR AT KITCHEN/CARPORT AREA. NOT
 SUBMITTED. MAKE SURE CORRECT SIZE IS
 SUBMITTED. SEE PLANS.
 G) SINGLE HUNG WINDOWS. NEED UPDATED
 NOA #05-0729.03. GO TO THE DCA WEBSITE
 WWW.FLORIDABUILDING.ORG TO DOWNLOAD
 APPROVED CURRENT NOA. SEARCH FOR FL#6585
  
 5- DESIGNER OF RECORD TO REVIEW AND
 APPROVE IN WRITTING (OR USE STANDARD
 REVIEW STAMP) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS
 TO FBC 2004. NEED TO PROVIDE REVISED
 LIST OF PRODUCT APPROVAL ACCORDING TO
 THE COMMENTS ON ITEM #4 ABOVE.
  
 6- DRAWINGS WERE STAMPED FOR IMPACT FEES
 ON 12-07-05. PERMIT APPLICATION WAS
 SUBMITTED ON 2-15-06. PLANS TO BE
 RE-STAMPED BY PALM BEACH COUNTY TO
 VERIFY THAT NO ADDITIONAL FEES ARE DUE
 SINCE IMPACT FEES CHANGED AFTER JANUARY
 13,2006. BRING BACK PAID RECEIPT AND
 RE-STAMPED PLANS. MAKE SURE THE RE-STAMP
 DRAWINGS ARE THE REVISED ONES.
  
 7- REVISE INFORMATION IN THE ENERGY
 CALCULATIONS: CONTRACTOR IS MI CASA
 BUILDERS, NOT T & F GENERAL CONTRACTING.
  
 8- PROVIDE 2 SIGNED AND SEALED COPIES
 OF THE SOIL TEST REPORT. REPORT IS
 MISSING THE FIRM CERTIFICATE OF
 AUTHORIZATION NUMBER AND THE ENGINEER'S
 LICENSE NUMBER AS REQUIRED BY CHAPTER
 471 FLORIDA STATUTES AND 61G15-23.002 OF
 FLORIDA ADMINISTRATIVE CODE.
  
 9- STORM SHUTTERS: A) PROVIDE FLORIDA
 OR LOCAL PRODUCT APPROVAL FOR STORM
 SHUTTERS TO BE USED. INFORMATION
 SUBMITTED IS INCOMPLETE.
 B) PROVIDE KEY PLAN.
 C) PROVIDE COMPLETE INSTALLATION
 SCHEDULE. SEE ATTACHED SAMPLE, WHICH HAS
 ALL INFORMATION REQ'D FOR PLAN REVIEW.
  
 10- SHEET A-2, S-1: A) REVISE ORIGINAL
 DRAWING. HAND WRITTEN REVISIONS ARE NOT
 ACCEPTABLE. UPDATE ALL INFORMATION ON
 EMERGENCY EGRESS WINDOWS NOTES. SEE 2004
 RESIDENTIAL CODE AND COMMENTS ON PLANS.
 B) GENERAL NOTES: SPECIFY CURRENT
 FLORIDA BUILDING CODE FOR WHICH BUILDING
 WAS DESIGNED. "AS ADOPTED BY THE COUNTY"
 IS NOT AN SPECIFIC CODE.
 C) DETAIL F1: SHOW GRADE LEVEL TO
 VERIFY COMPLIANCE WITH SEC. R403.1.4
 2004 RESIDENTIAL CODE.
 D) FOUNDATION PLAN: SHOW DROP FROM
 MAIN CONCRETE SLAB TO THE CARPORT AT
 ENTRY DOOR AND KITCHEN DOOR. ALSO AT
 SLIDING GLASS DOORS. SEE PLAN.
 E) SPECIFY CONCRETE SLAB JOINTS OR
 SPECIFY SUPPORTS SPACING FOR WWM AS
 REQUIRED BY SEC. R506.2.4 EXCEPTION #2
 OF 2004 RESIDENTIAL CODE.
 F) DELETE MECHANICAL NOTE IF IT
 DOESN'T APPLY TO THIS PROJECT.
 G) UPDATE REFERENCE INFORMATION FOR
 OPENINGS. SEE 2004 RESIDENTIAL CODE AND
 COMMENTS ON PLANS.
  
 11- SHEET S-2: REVISE ORIGINAL DRAWINGS.
 HAND WRITTEN REVISIONS ARE NOT
 ACCEPTABLE.
 A) TRUSS ANCHOR SCHEDULE: REVISE TYPO.
 CORRECT CONNECTOR IS TAPL16 NOT TALP16.
 B) CONNECTOR A5 IS A WOOD TO WOOD
 CONNECTOR. NEED TO SPECIFY WOOD TO
 MASONRY CONNECTOR. REVISE AS REQUIRED.
 C) SPECIFY WHERE DOES DETAIL F/A-6
 APPLIES TO?. NEW HAND WRITTEN REVISION
 CALLS FOR THIS DETAIL AT WALL BETWEEN
 CARPORT AND KITCHEN AREA. THEREFORE,
 NEED TO REVISE ROOF FRAMING TRUSS LAYOUT
 TO MATCH THIS CONDITION. CURRENT ROOF
 FRAMING PLAN DOESN'T CALL FOR TRUSS
 ABOVE THIS WALL. REVISE AS REQUIRED.
 D) REVISE LENGTH FOR PRECAST LINTEL
 #2. SEE PLANS FOR CORRECT SPAN.
 E) NEW ADDING STRAP DETAIL 1:
 * INCLUDE THIS DETAIL IN THE ORIGINAL
 DRAWING S-2.
 ** CONNECTOR USP RT24T IS A WOOD TO
 WOOD CONNECTOR. NEED TO SPECIFY WOOD TO
 MASONRY CONNECTOR. REVISE AS REQUIRED.
 *** CONNECTOR USP RT24T DOESN'T HAVE
 ENOUGH HOLES TO PUT 12 NAILS ON TRUSS
 SIDE. REVISE AS REQUIRED.
 **** CONNECTOR SIMPSON MSTA 24 IS ALSO
 A WOOD TO WOOD CONNECTOR. NEED TO
 SPECIFY WOOD TO MASONRY CONNECTOR FOR
 PROPOSED INSTALLATION. REVISE AS REQ'D.
  
 12- SHEET D-1: REVISE ORIGINAL DRAWING.
 HAND WRITTEN REVISIONS ARE NOT
 ACCEPTABLE.
 A) DELETE WINDOW MULLION DETAIL IF IT
 DOESN'T APPLY.
 B) TYPICAL 1 STORY SECTION: OVERHANG
 IS SHOWN INCORRECTLY. MISSING THE TRUSS
 LEG THAT ALLOWS PLACEMENT OF ATTIC
 VENTS. REVISE DETAIL AS REQUIRED.
 C) SHOW GRADE LEVEL TO VERIFY
 COMPLIANCE WITH R403.1.4 2004 RES. CODE.
 D) UPDATE ALL REFERENCE STANDARDS
 SPECIFIED IN THEGENERAL NOTES. SEE
 2004 RESIDENTIAL CODE CHAPTER 43 FOR
 PROPER REFERENCE STANDARDS AND EDITION
 THAT ARE ADOPTED BY THE CODE.
 E) NEW TYP. 1 STORY SECTION:
 * PROVIDE THIS INFORMATION ON ORIGINAL
 DRAWING.
 ** CLARIFY ATTIC VENTILATION. IS IT 4"
 VENTS OR 6"X22" VENTS. IF IT'S 4", THEN
 IS IT CONTINUOUS OR NOT?. IF IS 6"X22"
 VENTS, THEN SPECIFY LOCATION. "NO LESS
 THAN 1:150 IS NOT ENOUGH INFORMATION.
 *** WHERE IS THE UPLIFT TABLE?.
  
  
 13- PLEASE RETURN REVIEWED SET AFTER
 CORECTIONS ARE DONE TO THE ORIGINAL
 DRAWINGS TO EXPEDITE REVIEW PROCESS.
 THIS WAS NOT DONE ON FIRST RE-SUBMITTAL.
 PROVIDING THIS SET REALLY EXPEDITES THE
 REVIEW TIME.
  
 14- A) PROVIDE SURVEY SHOWING NEW HOUSE
 FOOTPRINT AND SETBACKS. THIS WILL ALSO
 TAKE CARE OF ZONING COMMENTS.
 B) PROVIDE SURVEY WITH ORIGINAL SEAL
 AND SIGNATURE AS REQUIRED BY CHAPTER 472
 OF FLORIDA STATUTES.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712