2006-06-29 00:00:00 | BUILDING REVIEW 2ND CHECKLIST: |
| 1- WILL NEED RE-RECORDED NOTICE OF |
| COMMENCEMENT. RECORDED NOC WILL EXPIRE |
| BY 6-30-06 IF WORK IS NOT STARTED BY |
| THEN. SEC. 713.13.9(2) FL. STATUTES. |
| |
| 2- REVISE ORIGINAL DWGS. HAND WRITTEN |
| REVISIONS ARE NOT ACCEPTABLE. PROVIDE |
| BATHROOM WITH DOOR THAT ALLOWS 29" MIN. |
| CLEAR OPENING. |
| SECTION R322 2004 RESIDENTIAL CODE. |
| |
| 3- SPECIFY ATTIC ACCESS AND LOCATION. |
| NOTE: REVISE ORIGINAL DRAWING. |
| SEC. R807 2004 RESIDENTIAL CODE. |
| |
| 4- RULE 9B-72 OF DCA REQUIRES FLORIDA OR |
| LOCAL PRODUCT APPROVAL FOR: |
| A) PRECAST LINTELS. INFORMATION WAS |
| NOT SUBMITTED AND BE AWARE THAT DADE |
| COUNTY NOA #03-0605.05 IS EXPIRED. NEED |
| TO PROVIDE CURRENT ONE. |
| B) ALL STRUCTURAL CONNECTORS SPECIFIED |
| ON PLANS. INFORMATION SUBMITTED IS NOT A |
| PRODUCT APPROVAL REPORT. AND NEED |
| PRODUCT APPROVAL FOR ALL CONNECTORS |
| SPECIFIED ON PLANS. CHECK TRUSS ANCHOR |
| SCHEDULE AND ALL DETAILS TO SEE WHICH |
| CONNECTORS ARE SPECIFIED. |
| C) ROOF SHINGLES. NOT SUBMITTED. |
| D) SLIDING GLASS DOORS. PROVIDE DADE |
| COUNTY NOA WITH CLEAR & LEGIBLE DWGS. |
| ONE SUBMITTED IS NOT READABLE. |
| E) ENTRY DOOR. ONE SUBMITTED IS FOR |
| 6'-8" HIGH DOORS. NEED FOR 8'-0" HIGH |
| DOORS AS SPECIFIED ON PLANS. MAKE SURE |
| PRINTS ARE CLEAR AND LEGIBLE. |
| F) DOOR AT KITCHEN/CARPORT AREA. NOT |
| SUBMITTED. MAKE SURE CORRECT SIZE IS |
| SUBMITTED. SEE PLANS. |
| G) SINGLE HUNG WINDOWS. NEED UPDATED |
| NOA #05-0729.03. GO TO THE DCA WEBSITE |
| WWW.FLORIDABUILDING.ORG TO DOWNLOAD |
| APPROVED CURRENT NOA. SEARCH FOR FL#6585 |
| |
| 5- DESIGNER OF RECORD TO REVIEW AND |
| APPROVE IN WRITTING (OR USE STANDARD |
| REVIEW STAMP) ALL PRODUCT APPROVALS AS |
| REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS |
| TO FBC 2004. NEED TO PROVIDE REVISED |
| LIST OF PRODUCT APPROVAL ACCORDING TO |
| THE COMMENTS ON ITEM #4 ABOVE. |
| |
| 6- DRAWINGS WERE STAMPED FOR IMPACT FEES |
| ON 12-07-05. PERMIT APPLICATION WAS |
| SUBMITTED ON 2-15-06. PLANS TO BE |
| RE-STAMPED BY PALM BEACH COUNTY TO |
| VERIFY THAT NO ADDITIONAL FEES ARE DUE |
| SINCE IMPACT FEES CHANGED AFTER JANUARY |
| 13,2006. BRING BACK PAID RECEIPT AND |
| RE-STAMPED PLANS. MAKE SURE THE RE-STAMP |
| DRAWINGS ARE THE REVISED ONES. |
| |
| 7- REVISE INFORMATION IN THE ENERGY |
| CALCULATIONS: CONTRACTOR IS MI CASA |
| BUILDERS, NOT T & F GENERAL CONTRACTING. |
| |
| 8- PROVIDE 2 SIGNED AND SEALED COPIES |
| OF THE SOIL TEST REPORT. REPORT IS |
| MISSING THE FIRM CERTIFICATE OF |
| AUTHORIZATION NUMBER AND THE ENGINEER'S |
| LICENSE NUMBER AS REQUIRED BY CHAPTER |
| 471 FLORIDA STATUTES AND 61G15-23.002 OF |
| FLORIDA ADMINISTRATIVE CODE. |
| |
| 9- STORM SHUTTERS: A) PROVIDE FLORIDA |
| OR LOCAL PRODUCT APPROVAL FOR STORM |
| SHUTTERS TO BE USED. INFORMATION |
| SUBMITTED IS INCOMPLETE. |
| B) PROVIDE KEY PLAN. |
| C) PROVIDE COMPLETE INSTALLATION |
| SCHEDULE. SEE ATTACHED SAMPLE, WHICH HAS |
| ALL INFORMATION REQ'D FOR PLAN REVIEW. |
| |
| 10- SHEET A-2, S-1: A) REVISE ORIGINAL |
| DRAWING. HAND WRITTEN REVISIONS ARE NOT |
| ACCEPTABLE. UPDATE ALL INFORMATION ON |
| EMERGENCY EGRESS WINDOWS NOTES. SEE 2004 |
| RESIDENTIAL CODE AND COMMENTS ON PLANS. |
| B) GENERAL NOTES: SPECIFY CURRENT |
| FLORIDA BUILDING CODE FOR WHICH BUILDING |
| WAS DESIGNED. "AS ADOPTED BY THE COUNTY" |
| IS NOT AN SPECIFIC CODE. |
| C) DETAIL F1: SHOW GRADE LEVEL TO |
| VERIFY COMPLIANCE WITH SEC. R403.1.4 |
| 2004 RESIDENTIAL CODE. |
| D) FOUNDATION PLAN: SHOW DROP FROM |
| MAIN CONCRETE SLAB TO THE CARPORT AT |
| ENTRY DOOR AND KITCHEN DOOR. ALSO AT |
| SLIDING GLASS DOORS. SEE PLAN. |
| E) SPECIFY CONCRETE SLAB JOINTS OR |
| SPECIFY SUPPORTS SPACING FOR WWM AS |
| REQUIRED BY SEC. R506.2.4 EXCEPTION #2 |
| OF 2004 RESIDENTIAL CODE. |
| F) DELETE MECHANICAL NOTE IF IT |
| DOESN'T APPLY TO THIS PROJECT. |
| G) UPDATE REFERENCE INFORMATION FOR |
| OPENINGS. SEE 2004 RESIDENTIAL CODE AND |
| COMMENTS ON PLANS. |
| |
| 11- SHEET S-2: REVISE ORIGINAL DRAWINGS. |
| HAND WRITTEN REVISIONS ARE NOT |
| ACCEPTABLE. |
| A) TRUSS ANCHOR SCHEDULE: REVISE TYPO. |
| CORRECT CONNECTOR IS TAPL16 NOT TALP16. |
| B) CONNECTOR A5 IS A WOOD TO WOOD |
| CONNECTOR. NEED TO SPECIFY WOOD TO |
| MASONRY CONNECTOR. REVISE AS REQUIRED. |
| C) SPECIFY WHERE DOES DETAIL F/A-6 |
| APPLIES TO?. NEW HAND WRITTEN REVISION |
| CALLS FOR THIS DETAIL AT WALL BETWEEN |
| CARPORT AND KITCHEN AREA. THEREFORE, |
| NEED TO REVISE ROOF FRAMING TRUSS LAYOUT |
| TO MATCH THIS CONDITION. CURRENT ROOF |
| FRAMING PLAN DOESN'T CALL FOR TRUSS |
| ABOVE THIS WALL. REVISE AS REQUIRED. |
| D) REVISE LENGTH FOR PRECAST LINTEL |
| #2. SEE PLANS FOR CORRECT SPAN. |
| E) NEW ADDING STRAP DETAIL 1: |
| * INCLUDE THIS DETAIL IN THE ORIGINAL |
| DRAWING S-2. |
| ** CONNECTOR USP RT24T IS A WOOD TO |
| WOOD CONNECTOR. NEED TO SPECIFY WOOD TO |
| MASONRY CONNECTOR. REVISE AS REQUIRED. |
| *** CONNECTOR USP RT24T DOESN'T HAVE |
| ENOUGH HOLES TO PUT 12 NAILS ON TRUSS |
| SIDE. REVISE AS REQUIRED. |
| **** CONNECTOR SIMPSON MSTA 24 IS ALSO |
| A WOOD TO WOOD CONNECTOR. NEED TO |
| SPECIFY WOOD TO MASONRY CONNECTOR FOR |
| PROPOSED INSTALLATION. REVISE AS REQ'D. |
| |
| 12- SHEET D-1: REVISE ORIGINAL DRAWING. |
| HAND WRITTEN REVISIONS ARE NOT |
| ACCEPTABLE. |
| A) DELETE WINDOW MULLION DETAIL IF IT |
| DOESN'T APPLY. |
| B) TYPICAL 1 STORY SECTION: OVERHANG |
| IS SHOWN INCORRECTLY. MISSING THE TRUSS |
| LEG THAT ALLOWS PLACEMENT OF ATTIC |
| VENTS. REVISE DETAIL AS REQUIRED. |
| C) SHOW GRADE LEVEL TO VERIFY |
| COMPLIANCE WITH R403.1.4 2004 RES. CODE. |
| D) UPDATE ALL REFERENCE STANDARDS |
| SPECIFIED IN THEGENERAL NOTES. SEE |
| 2004 RESIDENTIAL CODE CHAPTER 43 FOR |
| PROPER REFERENCE STANDARDS AND EDITION |
| THAT ARE ADOPTED BY THE CODE. |
| E) NEW TYP. 1 STORY SECTION: |
| * PROVIDE THIS INFORMATION ON ORIGINAL |
| DRAWING. |
| ** CLARIFY ATTIC VENTILATION. IS IT 4" |
| VENTS OR 6"X22" VENTS. IF IT'S 4", THEN |
| IS IT CONTINUOUS OR NOT?. IF IS 6"X22" |
| VENTS, THEN SPECIFY LOCATION. "NO LESS |
| THAN 1:150 IS NOT ENOUGH INFORMATION. |
| *** WHERE IS THE UPLIFT TABLE?. |
| |
| |
| 13- PLEASE RETURN REVIEWED SET AFTER |
| CORECTIONS ARE DONE TO THE ORIGINAL |
| DRAWINGS TO EXPEDITE REVIEW PROCESS. |
| THIS WAS NOT DONE ON FIRST RE-SUBMITTAL. |
| PROVIDING THIS SET REALLY EXPEDITES THE |
| REVIEW TIME. |
| |
| 14- A) PROVIDE SURVEY SHOWING NEW HOUSE |
| FOOTPRINT AND SETBACKS. THIS WILL ALSO |
| TAKE CARE OF ZONING COMMENTS. |
| B) PROVIDE SURVEY WITH ORIGINAL SEAL |
| AND SIGNATURE AS REQUIRED BY CHAPTER 472 |
| OF FLORIDA STATUTES. |
| |