Plan Review Notes
Plan Review Notes For Permit 06020693
Permit Number 06020693
Review Stop E
Sequence Number 1
Notes
Date Text
2006-02-24 00:00:00*********** UNSAT ************
  
 ** PLEASE KNOW, PLANS ARE NOT COMPLETE
 AT THIS TIME. PLEASE ALSO SEE NUMEROUS
 ELECTRICAL CODE COMPLIANCE NOTES BELOW.
  
  
 1)NOTE: PLEASE SUBMIT AN ELECTRICAL
 RISER DIAGRAM FOR CODE COMPLIANCE,
 SEC'S, AWG'S, GROUNDING ELECTRODE SYSTEM
 ETC ETC
 215.5
  
 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 3) NOTE: PLEASE LIST ALL THE REQ'D
 DEDICATED BATH(S) CIRCUIT(S) ON PANEL
 SCHEDULE. SHALL BE 20A AND #12 AWG. PER
 210.52D, 210.11C3
  
 4)NOTE: PLEASE SEE BATH RMS MISSING THE
 REQUIRED GFI RECEPT WITHIN 3' OF LAV'S.
 210.52D, 210.8A
  
 5)NOTE: PLEASE SEE MISSING COUNTERSPACE
 GFI'S PER 210.52C1
 PLEASE ALSO SEE WHAT APPEARS TO GFI'S
 BEHIND THE SINK? IF THESE ARE FOR A DISH
 OR DISPOSAL, THEY ARE NOT REQUIED TO BE
 GFI AND SHOULD BE NOTED FOR PURPOSE AND
 LOCATION.
  
 6)NOTE: PLEASE SEE MISSING DISCONNECT
 REQUIRED FOR HWH. 422.31
  
 7)NOTE: PLEASE VERIFY PLANS SHOWS
 STACKABLE WASHRE/DRYER HOWEVER PANEL
 SCHEDULE DOES NOT INDICATE THIS?
 215.5
  
 8)NOTE: PLEASE CORRELATE PANEL SCHEDULE
 SIZE. SHOWS 150 AND 200A'S??
 215.5
  
 9)NOTE: PLEASE SEE MISSING DISCONNECTS
 FOR BOTH THE AHU AND CU. 440.11.
 PLANS APPEAR TO SHOW RECEPTS FOR EACH??
 PLUG IN TYPE UNITS ARE NOT PERMITTED.
 422.31 ETC
  
 10)NOTE: PLEASE LIST "ALL" THE REQUIRED
 ARC FAULT PROTECTED CIRCUIT. PLEASE SEE
 THE FOLLOWING NOTE. PLEASE ALSO SEE
 NOTES ON ELECTRICAL PLANS MENTIONS TO
 CIRCUIT THE SD'S TO THE KITCHEN OR BATH
 LT CIRCUIT? THIS IS OK, HOWEVER IF THE
 SD'S ARE CIRCUITED TO EITHER OFTHESE,
 THEN THEY WOULD BE REQUIRED TO BE AFCI
 PROTECTED CIRCUITS AND SHOULD ALSO BE
 LISTED.
 210.12
  
 11)NOTE: PLEASE SEE PLANS ONLY SEEM TO
 INDICATE ONE ARC FAULT CIRCUIT AND THIS
 IS ALSO SHOWN AS THE ONLY CIRCUIT FOR
 ALL THREE BEDRMS FOR LTS, SD'S FANS, AND
 RECEPTS?? PLEASE SEE 240.4,310.16 ETC AS
 AS SHOWN THIS ONE CIRCUIT WOULD BE
 OVERLOADED.
 215.5
  
 12)NOTE: PLEASE SEE MANY LOCATIONS FOR
 MISSING RECEPTS PER 210.52
  
 13)NOTE: PLEASE SEE MISSING EGRESS LTS,
 CONTROL ETC PER 210.70, LS 101 7.8 ETC
 ALL LOCATIONS ON PLANS.
  
 14)NOTE: PLEASE SEE ALL CIRCUITING ON
 PANEL SCHEDULE SHOWS ALL CIRCUITS AS
 "2-POLE" WHICH INDICATES ALL AS 240V?
 PLEASE CORRECT.
 215.5
  
 15)NOTE: PLEASE BE SURE PLANS REFERENCE
 THE CURRENT CODE. (2002 NEC ).
  
 16)NOTE: PLEASE SEE THE BLDG REVIEW
 COMMENTS AS THE VALUE OF $60K IS WAY
 LOAW FOR VALUATION OF BUILDING THIS NEW
 3/2. FBC 108.3
  
 17)NOTE: PLEASE SEE PLANS ALSO REFERENCE
 THE 2001 FBC, WHEN AS OF OCT 1ST, 2005
 THE STATE OF FLORIDA ADOPTED THE 2004
 FBC.
 PLEASE ADJUST PLANS.
  
 18)NOTE: PLEASE ALSO SEE BLDG REVIEW
 NOTES, AS ONLY PERMIT APPLICATIONS
 SUBMIITTED BEFORE JAN 13, 2006 FALL
 UNDER THE OLD PALM BEACH COUNTY IMAPCT
 FEES, PLEASE KNOW, PLANS WILL BE
 REQUIRED TO GO BACK TO PBC TO BE
 REVIEWED AND RE-STAMPED AS PLANS WERE
 NOT SUBMITTED UNTIL FEB 15, 2006.
  
 ** PLEASE KNOW, DUE TO THE EXTENT OF
 ELECTRICAL COMMENTS, THERE MAY BE
 FURTHER COMMENTS ONCE PLANS ARE
 COMPLETED.
  
 ** PLEASE REMOVE ALL OLD/VOIDED SHEETS
 AND ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 ONE SET OF OLD/VOIDED SHEETS SHOULD BE
 SUBMITTED FOR REFERENCE ONLY.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]