2006-02-24 00:00:00 | *********** UNSAT ************ |
| |
| ** PLEASE KNOW, PLANS ARE NOT COMPLETE |
| AT THIS TIME. PLEASE ALSO SEE NUMEROUS |
| ELECTRICAL CODE COMPLIANCE NOTES BELOW. |
| |
| |
| 1)NOTE: PLEASE SUBMIT AN ELECTRICAL |
| RISER DIAGRAM FOR CODE COMPLIANCE, |
| SEC'S, AWG'S, GROUNDING ELECTRODE SYSTEM |
| ETC ETC |
| 215.5 |
| |
| 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| RATED FOR THE AVAILABLE FAULT CURRENT. |
| PER 110.9/215.5 |
| |
| 3) NOTE: PLEASE LIST ALL THE REQ'D |
| DEDICATED BATH(S) CIRCUIT(S) ON PANEL |
| SCHEDULE. SHALL BE 20A AND #12 AWG. PER |
| 210.52D, 210.11C3 |
| |
| 4)NOTE: PLEASE SEE BATH RMS MISSING THE |
| REQUIRED GFI RECEPT WITHIN 3' OF LAV'S. |
| 210.52D, 210.8A |
| |
| 5)NOTE: PLEASE SEE MISSING COUNTERSPACE |
| GFI'S PER 210.52C1 |
| PLEASE ALSO SEE WHAT APPEARS TO GFI'S |
| BEHIND THE SINK? IF THESE ARE FOR A DISH |
| OR DISPOSAL, THEY ARE NOT REQUIED TO BE |
| GFI AND SHOULD BE NOTED FOR PURPOSE AND |
| LOCATION. |
| |
| 6)NOTE: PLEASE SEE MISSING DISCONNECT |
| REQUIRED FOR HWH. 422.31 |
| |
| 7)NOTE: PLEASE VERIFY PLANS SHOWS |
| STACKABLE WASHRE/DRYER HOWEVER PANEL |
| SCHEDULE DOES NOT INDICATE THIS? |
| 215.5 |
| |
| 8)NOTE: PLEASE CORRELATE PANEL SCHEDULE |
| SIZE. SHOWS 150 AND 200A'S?? |
| 215.5 |
| |
| 9)NOTE: PLEASE SEE MISSING DISCONNECTS |
| FOR BOTH THE AHU AND CU. 440.11. |
| PLANS APPEAR TO SHOW RECEPTS FOR EACH?? |
| PLUG IN TYPE UNITS ARE NOT PERMITTED. |
| 422.31 ETC |
| |
| 10)NOTE: PLEASE LIST "ALL" THE REQUIRED |
| ARC FAULT PROTECTED CIRCUIT. PLEASE SEE |
| THE FOLLOWING NOTE. PLEASE ALSO SEE |
| NOTES ON ELECTRICAL PLANS MENTIONS TO |
| CIRCUIT THE SD'S TO THE KITCHEN OR BATH |
| LT CIRCUIT? THIS IS OK, HOWEVER IF THE |
| SD'S ARE CIRCUITED TO EITHER OFTHESE, |
| THEN THEY WOULD BE REQUIRED TO BE AFCI |
| PROTECTED CIRCUITS AND SHOULD ALSO BE |
| LISTED. |
| 210.12 |
| |
| 11)NOTE: PLEASE SEE PLANS ONLY SEEM TO |
| INDICATE ONE ARC FAULT CIRCUIT AND THIS |
| IS ALSO SHOWN AS THE ONLY CIRCUIT FOR |
| ALL THREE BEDRMS FOR LTS, SD'S FANS, AND |
| RECEPTS?? PLEASE SEE 240.4,310.16 ETC AS |
| AS SHOWN THIS ONE CIRCUIT WOULD BE |
| OVERLOADED. |
| 215.5 |
| |
| 12)NOTE: PLEASE SEE MANY LOCATIONS FOR |
| MISSING RECEPTS PER 210.52 |
| |
| 13)NOTE: PLEASE SEE MISSING EGRESS LTS, |
| CONTROL ETC PER 210.70, LS 101 7.8 ETC |
| ALL LOCATIONS ON PLANS. |
| |
| 14)NOTE: PLEASE SEE ALL CIRCUITING ON |
| PANEL SCHEDULE SHOWS ALL CIRCUITS AS |
| "2-POLE" WHICH INDICATES ALL AS 240V? |
| PLEASE CORRECT. |
| 215.5 |
| |
| 15)NOTE: PLEASE BE SURE PLANS REFERENCE |
| THE CURRENT CODE. (2002 NEC ). |
| |
| 16)NOTE: PLEASE SEE THE BLDG REVIEW |
| COMMENTS AS THE VALUE OF $60K IS WAY |
| LOAW FOR VALUATION OF BUILDING THIS NEW |
| 3/2. FBC 108.3 |
| |
| 17)NOTE: PLEASE SEE PLANS ALSO REFERENCE |
| THE 2001 FBC, WHEN AS OF OCT 1ST, 2005 |
| THE STATE OF FLORIDA ADOPTED THE 2004 |
| FBC. |
| PLEASE ADJUST PLANS. |
| |
| 18)NOTE: PLEASE ALSO SEE BLDG REVIEW |
| NOTES, AS ONLY PERMIT APPLICATIONS |
| SUBMIITTED BEFORE JAN 13, 2006 FALL |
| UNDER THE OLD PALM BEACH COUNTY IMAPCT |
| FEES, PLEASE KNOW, PLANS WILL BE |
| REQUIRED TO GO BACK TO PBC TO BE |
| REVIEWED AND RE-STAMPED AS PLANS WERE |
| NOT SUBMITTED UNTIL FEB 15, 2006. |
| |
| ** PLEASE KNOW, DUE TO THE EXTENT OF |
| ELECTRICAL COMMENTS, THERE MAY BE |
| FURTHER COMMENTS ONCE PLANS ARE |
| COMPLETED. |
| |
| ** PLEASE REMOVE ALL OLD/VOIDED SHEETS |
| AND ONLY INSERT NEW REVISED SHEETS INTO |
| COMPLETE SETS FOR REVIEW AND STAMPING. |
| ONE SET OF OLD/VOIDED SHEETS SHOULD BE |
| SUBMITTED FOR REFERENCE ONLY. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE IN CONTACTING |
| THIS OFFICE. |
| |