2006-03-17 00:00:00 | BUILDING REVIEW CHECKLIST: |
| 1- NEED RECORDED NOTICE OF COMMENCEMENT. |
| |
| 2- PROVIDE BATHROOM WITH DOOR THAT |
| ALLOWS 29" MIN. CLEAR OPENING. SECTION |
| R322 2004 RESIDENTIAL CODE. |
| |
| 3- SPECIFY ATTIC ACCESS AND LOCATION. |
| SEC. R807 2004 RESIDENTIAL CODE. |
| |
| 4- PROVIDE DRAINAGE PLAN AS REQUIRED BY |
| SEC. R401.3 2004 RESIDENTIAL CODE. |
| |
| 5- RULE 9B-72 OF DCA REQUIRES FLORIDA OR |
| LOCAL PRODUCT APPROVAL FOR: |
| A) PRECAST LINTELS. |
| B) TRUSS ANCHORS AND ALL STRUCTURAL |
| CONNECTORS SPECIFIED IN PLANS. SEE PLANS |
| C) ROOF SHINGLES. |
| D) SLIDING GLASS DOORS. |
| E) ENTRY DOOR. |
| F) DOOR AT KITCHEN/CARPORT AREA. |
| G) SINGLE HUNG WINDOWS. |
| |
| ***NOTE: |
| DADE COUNTY NOA'S ALONE ARE NOT |
| AUTOMATICALLY STATEWIDE FLORIDA PRODUCT |
| APPROVALS. GO TO THE DCA FLORIDA WEBSITE |
| WWW.FLORIDABUILDING.ORG TO DOWNLOAD |
| APPROVED FLORIDA PRODUCT APPROVALS. |
| OTHERWISE, MANUFACTURER TO APPLY FOR |
| LOCAL PRODUCT APPROVALS. |
| |
| 6- DESIGNER OF RECORD TO REVIEW AND |
| APPROVE IN WRITTING (OR USE STANDARD |
| REVIEW STAMP) ALL PRODUCT APPROVALS AS |
| REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS |
| TO FBC 2004. |
| |
| 7- DRAWINGS WERE STAMPED FOR IMPACT FEES |
| ON 12-07-05. PERMIT APPLICATION WAS |
| SUBMITTED ON 2-15-06. PLANS TO BE |
| RE-STAMPED BY PALM BEACH COUNTY TO |
| VERIFY THAT NO ADDITIONAL FEES ARE DUE |
| SINCE IMPACT FEES CHANGED AFTER JANUARY |
| 13,2006. |
| |
| 8- OWES $710.28 FOR UPDATED VALUATION |
| AND RADON FEES. |
| |
| 9- REVISE INFORMATION IN THE ENERGY |
| CALCULATIONS: A) PERMITTING OFFICE IS |
| CITY OF WEST PALM BEACH, NOT PALM BEACH |
| COUNTY. |
| B) JURISDICTION NUMBER IS 604700, NOT |
| 601000. |
| |
| 10- PROVIDE 2 SIGNED AND SEALED COPIES |
| OF THE SOIL TEST REPORT. ONLY ONE |
| SUBMITTED. |
| |
| 11- STORM SHUTTERS: A) PROVIDE FLORIDA |
| OR LOCAL PRODUCT APPROVAL FOR STORM |
| SHUTTERS TO BE USED. |
| B) PROVIDE KEY PLAN. |
| C) PROVIDE COMPLETE INSTALLATION |
| SCHEDULE. SEE ATTACHED SAMPLE, WHICH HAS |
| ALL INFORMATION REQ'D FOR PLAN REVIEW. |
| |
| 12- SHEET A-2, S-1: A) UPDATE ALL |
| INFORMATION ON EMERGENCY EGRESS WINDOWS |
| NOTES. SEE 2004 RESIDENTIAL CODE AND |
| COMMENTS ON PLANS. |
| B) GENERAL NOTES: SPECIFY CURRENT |
| FLORIDA BUILDING CODE FOR WHICH BUILDING |
| WAS DESIGNED. "AS ADOPTED BY THE COUNTY" |
| IS NOT AN SPECIFIC CODE. |
| C) DETAIL F1: SHOW GRADE LEVEL TO |
| VERIFY COMPLIANCE WITH SEC. R403.1.4 |
| 2004 RESIDENTIAL CODE. |
| D) FOUNDATION PLAN: SHOW DROP FROM |
| MAIN CONCRETE SLAB TO THE CARPORT AT |
| ENTRY DOOR AND KITCHEN DOOR. ALSO AT |
| SLIDING GLASS DOORS. SEE PLAN. |
| E) SPECIFY CONCRETE SLAB JOINTS OR |
| SPECIFY SUPPORTS SPACING FOR WWM AS |
| REQUIRED BY SEC. R506.2.4 EXCEPTION #2 |
| OF 2004 RESIDENTIAL CODE. |
| F) DELETE MECHANICAL NOTE IF IT |
| DOESN'T APPLY TO THIS PROJECT. |
| G) UPDATE REFERENCE INFORMATION FOR |
| OPENINGS. SEE 2004 RESIDENTIAL CODE AND |
| COMMENTS ON PLANS. |
| |
| 13- SHEET S-2: A) TRUSS ANCHOR SCHEDULE: |
| REVISE TYPO. CORRECT CONNECTOR IS TAPL16 |
| NOT TALP16. |
| B) REVISE NUMBER OF FASTENERS |
| SPECIFIED FORTAPL16. SEE CATALOGUE. |
| OTHERWISE, PROVIDE COMPLETE ENGINEERING |
| CALCULATIONS FOR TYPE AND NUMBER OF |
| FASTENERS THAT DIFFER FROM THOSE TESTED |
| AND PUBLISHED BY THE MANUFACTURER. SEC. |
| 106.1.2 CITY AMENDMENTS TO FBC 2004. |
| C) CONNECTOR A5 IS A WOOD TO WOOD |
| CONNECTOR. NEED TO SPECIFY WOOD TO |
| MASONRY CONNECTOR. REVISE AS REQUIRED. |
| D) SPECIFY WHERE DOES DETAIL F/A-6 |
| APPLIES TO?. OR DELETE DETAILS THAT |
| DON'T APPLY TO THIS PROJECT. |
| E) REVISE LENGTH FOR PRECAST LINTEL |
| #2. SEE PLANS FOR CORRECT SPAN. |
| |
| 14- SHEET D-1: A) DELETE WINDOW MULLION |
| DETAIL IF IT DOESN'T APPLY. |
| B) TYPICAL 1 STORY SECTION: OVERHANG |
| IS SHOWN INCORRECTLY. MISSING THE TRUSS |
| LEG THAT ALLOWS PLACEMENT OF ATTIC |
| VENTS. REVISE DETAIL AS REQUIRED. |
| B) SHOW GRADE LEVEL TO VERIFY |
| COMPLIANCE WITH R403.1.4 2004 RES. CODE. |
| C) UPDATE ALL REFERENCE STANDARDS |
| SPECIFIED IN THEGENERAL NOTES. SEE |
| 2004 RESIDENTIAL CODE CHAPTER 43 FOR |
| PROPER REFERENCE STANDARDS AND EDITION |
| THAT ARE ADOPTED BY THE CODE. |
| |
| 15- PLEASE RETURN REVIEWED SET AFTER |
| CORECTIONS ARE DONE TO THE ORIGINAL |
| DRAWINGS TO EXPEDITE REVIEW PROCESS. |
| |