2006-02-21 00:00:00 | ******** UNSAT ************ |
| |
| |
| 1)NOTE: PLEASE SEE PLANS REFERENCE THE |
| 2001 FBC AND 2001 SBC. |
| PLEASE KNOW, THE SBC WENT OUT OF USE TEO |
| CODE CYCLES AGO. PLEASE ALSO KNOW, AS OF |
| OCT 1ST, 2005 THE NEW FBC IS 2004 |
| PLEASE ALSO SEE PLANS INDICATE"PALM |
| BEACH COUNTY" WHERE THE JOB IS LOCATED |
| IN THE CITY OF WEST PALM BEACH. |
| |
| 2)NOTE: PLEASE SEE MISSING KITCHEN GFI'S |
| PER 210.52C1 |
| |
| 3)NOTE: PLEASE SEE MISSING KITCHEN |
| PENINSULAR GFI PER 210.52C3 |
| |
| 4)NOTE: PLEASE SEE MISSING DEDICATED |
| BATH CIRCUITS PER 210.52D,210.11C3, MUST |
| BE 20A AND #12 MIN. |
| |
| 5)NOTE: PLEASE SEE MISSING AIC RATING |
| FOR MAINS AND AND SERVICE EQUIPMENT. |
| 110.9,215.5 |
| |
| 6)NOTE: PLEASE SEE 424.3B FOR OCP FOR |
| AHU HEAT. PLEASE ALSO VERIFY THE SIZE OF |
| THE HEAT FOR THIS SIZE OF A DWELLING |
| UNIT. 5KW SEEMS LOW. |
| PLEASE SEE 50A OCP IS HIGH FOR 5KW . |
| |
| 7)NOTE: PLEASE SEE NUMEROUS 15A CIRCUITS |
| ON PANEL SCHEDULE WHICH EXCEED THE |
| BRANCH CIRCUIT RATING. PLEASE SEE 1440 |
| VA PER 15A CIRCUITS, 1920VA FOR 20A |
| BRANCH CIRCUITS. |
| 240.4,310.16,ETC. |
| |
| 8)NOTE: PLEASE SEE BLDG REVIEW COMMENTS |
| WITH RESPECT TO THE CONSTRUCTION |
| VALUATION. PER 108.3 FBC ADMINISTRATIVE |
| SECTION ADOPTED INTO THE LOCAL |
| AMENDMENTS. |
| |
| ** PLEASEBE SURE TO REMOVE ALL |
| OLD/VOIDED SHEETS AND ONLY INSERT NEW |
| REVISED SHEETS INTO TWO COMPLETE SETS |
| FOR REVIEW AND STAMPING. |
| ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| |
| ** PLEASE SEE ANY COMMENTS FROM OTHER |
| TRADES WHICH MAY AFFECT ELECTRICAL |
| PLANS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| 561-805-6717 |
| [email protected] |