Plan Review Notes
Plan Review Notes For Permit 06020656
Permit Number 06020656
Review Stop E
Sequence Number 1
Notes
Date Text
2006-02-21 00:00:00******** UNSAT ************
  
  
 1)NOTE: PLEASE SEE PLANS REFERENCE THE
 2001 FBC AND 2001 SBC.
 PLEASE KNOW, THE SBC WENT OUT OF USE TEO
 CODE CYCLES AGO. PLEASE ALSO KNOW, AS OF
 OCT 1ST, 2005 THE NEW FBC IS 2004
 PLEASE ALSO SEE PLANS INDICATE"PALM
 BEACH COUNTY" WHERE THE JOB IS LOCATED
 IN THE CITY OF WEST PALM BEACH.
  
 2)NOTE: PLEASE SEE MISSING KITCHEN GFI'S
 PER 210.52C1
  
 3)NOTE: PLEASE SEE MISSING KITCHEN
 PENINSULAR GFI PER 210.52C3
  
 4)NOTE: PLEASE SEE MISSING DEDICATED
 BATH CIRCUITS PER 210.52D,210.11C3, MUST
 BE 20A AND #12 MIN.
  
 5)NOTE: PLEASE SEE MISSING AIC RATING
 FOR MAINS AND AND SERVICE EQUIPMENT.
 110.9,215.5
  
 6)NOTE: PLEASE SEE 424.3B FOR OCP FOR
 AHU HEAT. PLEASE ALSO VERIFY THE SIZE OF
 THE HEAT FOR THIS SIZE OF A DWELLING
 UNIT. 5KW SEEMS LOW.
 PLEASE SEE 50A OCP IS HIGH FOR 5KW .
  
 7)NOTE: PLEASE SEE NUMEROUS 15A CIRCUITS
 ON PANEL SCHEDULE WHICH EXCEED THE
 BRANCH CIRCUIT RATING. PLEASE SEE 1440
 VA PER 15A CIRCUITS, 1920VA FOR 20A
 BRANCH CIRCUITS.
 240.4,310.16,ETC.
  
 8)NOTE: PLEASE SEE BLDG REVIEW COMMENTS
 WITH RESPECT TO THE CONSTRUCTION
 VALUATION. PER 108.3 FBC ADMINISTRATIVE
 SECTION ADOPTED INTO THE LOCAL
 AMENDMENTS.
  
 ** PLEASEBE SURE TO REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW
 REVISED SHEETS INTO TWO COMPLETE SETS
 FOR REVIEW AND STAMPING.
 ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
  
 ** PLEASE SEE ANY COMMENTS FROM OTHER
 TRADES WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  