Plan Review Notes For Permit 06020589 |
Permit Number |
06020589 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2006-05-14 00:00:00 | ** REDLINED PLANS, | | | | PLEASE SEESD'S ARE NOW SHOWN | | ON CIRCUIT #2 WHICH DOES NOT INDICATE | | ARC FAULT PROTECTION AS REQ'D UDNER 2002 | | NEC 210.12B. | | SD'S CAN BE ON A-2, HOWEVER A AFCI TYOE | | BRKR WILL THEN BE REQUIRED. | | | | PLEASE SEE BATHS ARE NOW INDICATING ARC | | FAULT FOR BATHRMS? |
|