Plan Review Notes
Plan Review Notes For Permit 06020589
Permit Number 06020589
Review Stop M
Sequence Number 1
Notes
Date Text
2006-02-27 00:00:00*** DENIED ***
 1)ENERGY CALCULATIONS NEED TO BE ON FORM
 600A-04 (2004) PER FBC 13-600.3.A .
  
 2) MECHANICAL PLANS HAVE TO MUCH FLOOR
 PLAN INFOMATION ON THEMAND ARE
 DIFFICULT TO READ. CONSTRUCTION
 DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY. PER 2004 FBC 106.1.1 .
  
 3) TOTAL BTU'S ON E-CAL'S. ARE 25,800
 AND THE TOTAL BTU'S ON THE MECHANICAL
 PLANS ARE 36,000. THE BTU'S ON THE PLANS
 CAN NOT BE OVER THE E-CAL'S, PER 2004
 FBC CH. 13 .
  
 4) THE JOB ADDRESS NEEDS TO BE ON THE
 MECHANICAL PLANS.
  
 5)ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 SHALL BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN. PER
 FBC 104.2.1 .
  
 6) CONTRACTOR'S LICENSENUMBER NEED TO
 BE ON MECHANICAL PLANS.
  
 7) PLEASE SHOW COPPER LINE SIZES ON
 MECH. PLANS.
  
 8) PLEASE SHOW CONDENSATE DRAIN LINE ON
 MECH. PLANS.
  
 9) RETURN AIR TRANSFER DUCT NOT SIZED
 FROM BEDROOM #1 TO BEDROOM #2.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.