Date |
Text |
2006-02-15 00:00:00 | ******** UNSAT ************ |
| |
| 1)NOTE: PLEASE SEE MISSING FIRM LICENSE |
| NUMBER ON TITLE BLOCK FOR ARCHITECTUAL |
| FIRM. FAC 61G1-16.004, FS 481.219 |
| THIS IS REQUIRED FOR ALL SHEETS AND FOR |
| ALL TRADES WHETHER OR NOT COMMENT IS |
| MADE BY OTHER REVIEWER(S). |
| |
| 2)NOTE: PLEASE SEEELECTRICAL PLANS ARE |
| SIGNED , DATED AND SEALED BY AN |
| ELECTRICAL ENGINEER, HOWEVER PLANS DO |
| NOT CONTAIN ANY TITLE BLOCK FOR SAID |
| ENGINEER OF RECORD AS REQUIRED PER FAC |
| 61G15-23.002, FS 471.023 |
| |
| 3)NOTE: PLEASE VERIFY THE 1/2" CONDUIT |
| SHOWN FOR FUTURE PHONE. IT IS KNOWN TO |
| THIS OFFICE THE TELEPHONE COMPANY AND |
| CABLE COMPANY REQUIRES A MIN OF 3/4" |
| CONDUIT FOR UNDERGROUND INSTALLATIONS. |
| THIS IS FOR INFORMATIONAL PURPOSE ONLY |
| AS THIS IS NOT AN NEC REQUIREMENT. |
| |
| 4)NOTE: PLEASE CORRELATE LOAD FOR RANGE |
| IN LOAD CALCS WITH LOAD ON PANEL |
| SCHEDULE. |
| PLEASE VERIFY IF INDEED A 40A BRKR WILL |
| BE USED AS MOST RANGES REQUIRE A MIN OF |
| 50A. (RANGE RECEPT IS 50A) |
| PLEASE ALSO VERIFY WIRING METHODS TO BE |
| USED. PLANS INDICATE CONDUIT AND WIRING, |
| HOWEVER IF ROMEX IS USED, THE #8 SHOWN |
| WOULD BE REQUIRED TO BE INCREASED TO #6. |
| SEE 310.16, 60 DEGREE COL. |
| 215.5 |
| |
| 5)NOTE: PLEASE SEE SD'S ARE SHOWN BEING |
| WIRED TO MORE THAN ONE CIRCUIT. PLEASE |
| KNOW, THESE ARE REQUIRED TO BE WIRED |
| INLINE AND WILL NOT WORK AS SHOWN. |
| PLEASE BE SURE CIRCUIT SI ONE CONTAINING |
| ARC FAULT PROTECTION. |
| |
| 6)NOTE: PLEASE SEE ITEMS LISTED |
| "OFF"PANEL SCHEDULE. |
| |
| 7)NOTE: PLEASE SEE BATH CIRCUIT SHOWN AS |
| #15 AWG? MISPRINT. |
| PLEASE ALSO SEE BATH CIRCUITS ARE SHOWN |
| WITH ARC FAULT BRKRS? |
| |
| 8)NOTE: PLEASE SEE MISSING KITCHEN |
| COUNTERSPACE RECEPTS PER 210.52C1 |
| |
| 9)NOTE: PLEASE SEE MISSING REAR GFI |
| RECEPT PER 210.52E |
| |
| 10)NOTE: PLEASE SEE PANEL SCHEDULE |
| INDICATES LANSCAPE LTS, HOWEVER PLANS DO |
| NOT SHOW ANY. PLEASE KNOW, IF NONE SHOWN |
| ON PLANS, THEN LANDSCAPE LIGHTING WILL |
| BE REQUIRED TO BE UNDER A SEPARATE |
| PERMIT, WHICH WILL INCLUDE PERMIT, PLANS |
| AND FEE. |
| |
| ** PLEASE VERIFY WIRING METHOD, AS PLANS |
| INDICATE CONDUIT AND WIRING FOR ALL |
| CIRCUITS. IF SHOWN , ROMEX WOULD NOT BE |
| PERMITTED. |
| THIS IS ONLY A NOTE. |
| |
| PLEASE SEE ANY OTHER COMMENTS FROM OTHER |
| REVIEWERS WHICH MAY AFFECT ELECTRICAL |
| PLANS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE ON CONTACTING |
| THIS OFFICE. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| 561-805-6717 |
| [email protected] |
| |