Plan Review Notes For Permit 06020557 |
Permit Number |
06020557 |
|
Review Stop |
B |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2006-03-23 00:00:00 | 1) THE APPROVED ASSEMBLY SELECTED FROM | | THE NOA IS FOR A WOOD INSULATED ASSEMBLY | | WITH A -60PSF. THE ENGINEER LETTER | | REFERS ONLY TO THE ENHANCEMENTOF THE | | BASE SHEET. WHAT ABOUT THE ENHANCEMENT | | FOR THE INSULATION? | | | | 2) NOTE: THE INFORMATION OR LETTER FROM | | THE ENGINEER IS A STATEMENT AND NOT THE | | CALCULATIONS .GENERAL LIMITATION | | CLEARLY STATED THAT CALCULATIONS SHALL | | BE PREPARED BY A FLORIDA REGISTERDE | | PROFESSIONAL FOR THE ENHANCED UPLIFT | | PRESSURES. SO, SUBMIT THE CALCULATIONS | | FOR THE ENHANCED UPLIFT PRESSURES OF THE | | BASE SHEET AND THE INSULATION WHICH WILL | | MEET THE REQUIRED PRESSURE FOR THIS | | PROJECT. | | | | MYRON JACOBS | | BUILDING PLAN REVIEWER | | TEL:(561)805-6726 | | |
|