Plan Review Notes For Permit 06020557 |
Permit Number |
06020557 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-02-13 00:00:00 | 1) THE FLORIDA STATE SHEET DOES NOT | | MATCH THE NOA. | | | | 2) FBC 1609.7.1THE SYSTEM SELECTED | | FROM THE SUBMITTED FLAT ROOF PRODUCT | | APPROVAL NOA HAS A MAXIMUM DESIGN | | PRESSURE OF LESS THAN -89 PSF AND CITES | | GENERAL LIMITATION #9 (SEE PAGE 15 OF | | 21).GENERAL LIMITATION #9 PROHIBITS | | RATIONAL ANALYSIS OR EXTRAPOLATION TO | | ENHANCE THE UPLIFT PRESSURE AT PERIMETER | | AND CORNER AREAS BY REDUCING THE | | FASTENER SPACING IN THESE AREAS.EITHER | | SELECT AN ALTERNATIVE SYSTEM (OR PRODUCT | | APPROVAL) THAT DOES NOT CITE GENERAL | | LIMITATION #9.ALTERNATIVELY IF THE | | SELECTED SYSTEM DOES CITE GENERAL | | LIMITATION #9, IT MUST HAVE A MAXIMUM | | DESIGN PRESSURE THAT EXCEEDS THE | | PRESSURE IN ROOF ZONE 3 (TYPICALLY -89 | | PSF FOR MEAN ROOF HEIGHT OF 30 FEET OR | | LESS). |
|