2006-02-13 00:00:001) THE FLORIDA STATE SHEET DOES NOT
 MATCH THE NOA.
  
 2) FBC 1609.7.1THE SYSTEM SELECTED
 FROM THE SUBMITTED FLAT ROOF PRODUCT
 APPROVAL NOA HAS A MAXIMUM DESIGN
 PRESSURE OF LESS THAN -89 PSF AND CITES
 GENERAL LIMITATION #9 (SEE PAGE 15 OF
 21).GENERAL LIMITATION #9 PROHIBITS
 RATIONAL ANALYSIS OR EXTRAPOLATION TO
 ENHANCE THE UPLIFT PRESSURE AT PERIMETER
 AND CORNER AREAS BY REDUCING THE
 FASTENER SPACING IN THESE AREAS.EITHER
 SELECT AN ALTERNATIVE SYSTEM (OR PRODUCT
 APPROVAL) THAT DOES NOT CITE GENERAL
 LIMITATION #9.ALTERNATIVELY IF THE
 SELECTED SYSTEM DOES CITE GENERAL
 LIMITATION #9, IT MUST HAVE A MAXIMUM
 DESIGN PRESSURE THAT EXCEEDS THE
 PRESSURE IN ROOF ZONE 3 (TYPICALLY -89
 PSF FOR MEAN ROOF HEIGHT OF 30 FEET OR
 LESS).