Plan Review Notes
Plan Review Notes For Permit 06020459
Permit Number 06020459
Review Stop E
Sequence Number 1
Notes
Date Text
2006-03-01 00:00:00 
 PROVIDE A LOAD CALCULATION FOR THE
 INTENDED GENERATOR LOAD AND SHOW
 CIRCUITS SERVED.
 702.5 CAPACITY AND RATING.
 AN OPTIONAL STANDBY SYSTEM SHALL HAVE
 ADEQUATE CAPACITY AND RATING FOR THE
 SUPPLY OF ALL EQUIPMENT INTENDED TO BE
 OPERATED AT ONE TIME. OPTIONAL STANDBY
 SYSTEM EQUIPMENT SHALL BE SUITABLE FOR
 THE MAXIMUM AVAILABLE FAULT CURRENT AT
 ITS TERMINALS. THE USER OF THE OPTIONAL
 STANDBY SYSTEM SHALL BE PERMITTED TO
 SELECT THE LOAD CONNECTED TO THE SYSTEM.
  
 SUBMIT MANUFACTURERS SPECIFICATIONS FOR
 THE TRANSFER SWITCH.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  