2006-04-14 00:00:00************ REDLINED ************
  
  
 1) PLEASE SEE THE "EQUIPMENT GROUNDING
 CONDUCTOR" IS STILL BEING SHOWN FROM
 METER TO THE FIRST MEANS OF DISCONNECT.
 RESPONSE LTR FROM ENGINEER, MENTIONED
 THIS WAS REMOVED PER NOTES, HOWEVER THIS
 IS SHOWN ON RISER ON ALL THREE SETS.
 PLEASE SEE 250.6, 250.24B, THE "EQUIP
 GRNDING" IS ONLY INSTALLED AFTER THE
 FIRST MEANS OF DISC.
  
  
 2) PLEASE SEE THE PLANS NOW INDICATE A
 STRUCTURE WITH LT, THIS STRUCTURE WILL
 BE REQUIRED TO HAVE A MEANS OF DISC FOR
 LT AND ANY ELECTRICAL TO THIS STRUCTURE.
 THIS CAN BE A TOGGLE SW AND CAN BE
 LOCATED HIGHER ON STRUCTURE TO
 ALLEAVITATE INADVERTANT SWITCHING OF LT.
 225.31
  
 ** PLEASE KNOW, THE ABOVE WERE REDLINED
 ON PLANS AND THERE IS NO NEED FOR
 CORRECTIONS AT THIS TIME.
 ** PLEASE REVISE IF PLANS COME BACK OR
 ARE REVISED FOR ANY OTHER ELECTRICAL.
  
  
 IF THERE ARE ANY QUESTIONS, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE.
  