Notes |
Date |
Text |
2006-04-14 00:00:00 | ************ REDLINED ************ | | | | | | 1) PLEASE SEE THE "EQUIPMENT GROUNDING | | CONDUCTOR" IS STILL BEING SHOWN FROM | | METER TO THE FIRST MEANS OF DISCONNECT. | | RESPONSE LTR FROM ENGINEER, MENTIONED | | THIS WAS REMOVED PER NOTES, HOWEVER THIS | | IS SHOWN ON RISER ON ALL THREE SETS. | | PLEASE SEE 250.6, 250.24B, THE "EQUIP | | GRNDING" IS ONLY INSTALLED AFTER THE | | FIRST MEANS OF DISC. | | | | | | 2) PLEASE SEE THE PLANS NOW INDICATE A | | STRUCTURE WITH LT, THIS STRUCTURE WILL | | BE REQUIRED TO HAVE A MEANS OF DISC FOR | | LT AND ANY ELECTRICAL TO THIS STRUCTURE. | | THIS CAN BE A TOGGLE SW AND CAN BE | | LOCATED HIGHER ON STRUCTURE TO | | ALLEAVITATE INADVERTANT SWITCHING OF LT. | | 225.31 | | | | ** PLEASE KNOW, THE ABOVE WERE REDLINED | | ON PLANS AND THERE IS NO NEED FOR | | CORRECTIONS AT THIS TIME. | | ** PLEASE REVISE IF PLANS COME BACK OR | | ARE REVISED FOR ANY OTHER ELECTRICAL. | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE DO | | NOT HESITATE IN CONTACTING THIS OFFICE. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|