2006-03-16 00:00:00PAUL SCHMITZ
 [email protected]
 FBC 2004 PLUMBING CODE PLAN REVIEW
 AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPT.1, ADMINISTRATION, 2004 EDITION
 DENIED
 1) SHT L3IRRIGATION
 IF THE DESIGN PROFESSIONAL IS AN
 ARCHITECT OR ENGINEER LEGALLY REGISTERED
 UNDER THE LAWS OF THIS STATE REGULATING
 THE PRACTICE OF ARCHITECTURE AS PROVIDED
 FOR IN CHAPTER 481, FLORIDA STATUTES,
 PART I, OR ENGINEERING AS PROVIDED FOR
 IN CHAPTER 471, FLORIDA STATUTES, THEN
 HE OR SHE SHALL AFFIX HIS OR HER
 OFFICIAL SEAL, SIGNATURE AND DATE TO
 SAID DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA, AS REQUIRED BY
 FLORIDA STATUTE. IF THE DESIGN
 PROFESSIONAL IS A LANDSCAPE ARCHITECT
 REGISTERED UNDER THE LAWS OF THIS STATE
 REGULATING THE PRACTICE OF LANDSCAPE
 ARCHITECTURE AS PROVIDED FOR IN CHAPTER
 481, FLORIDA STATUTES, PART II, THEN HE
 OR SHE SHALL AFFIX HIS OR HER SEAL,
 SIGNATURE AND DATE TO SAID DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA AS
 DEFINED IN SECTION
 481.303(6)(A)(B)(C)(D), FS.
  
 2) SHT L3 LOCAL ORDINANCE #2583-95
 BACK FLOW PREVENTER REQUIRED ON THE
 WATER SERVICE TO THE IRRIGATION SYSTEM.
  
 END OF COMMENTS, QUESTIONS 561-805-6692
  