Plan Review Notes For Permit 06020373 |
Permit Number |
06020373 |
|
Review Stop |
G |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-02-10 00:00:00 | DENIED | | REFERENCE:FBC-2004 FUEL GAS | | | | THE FOLLOWING INFORMATION IS REQUIRED | | FOR GAS PERMIT: | | | | 1. SUBMIT AN ISOMETRIC DRAWING THAT | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | AND CORRESPONDING LENGTHS PER FBC-2004 | | FUEL GAS CODE. | | 2. SHOW THE TYPE OF PIPING MATERIAL | | BEING INSTALLED, ALL PIPE SIZES, AND | | TYPE OF REGULATORS. | | 3. CLEARLY SHOW THE LOCATION AND CAP- | | ACITY OF LP TANK(S), TYPE OF TANK (DOT | | OR ASME), THE DISTANCE OF THE TANK FROM | | THE BUILDING AND ADJACENT PROPERTY LINES | | THE DISTANCE OF THE TANK FROM ALL SOUR- | | CES OF IGNITION, OTHER CONTAINERS, BUILD | | INGS, AND THE LOCATION OF ANY BUILDING | | OPENINGS BELOW THE RELIEF VALVE OF THE | | TANK PER NFPA 58, TABLE 3-2.2.2. | | 4. CLEARLY INDICATE ON THE PLAN IF THE | | LP TANK IS ABOVE OR BELOW GROUND, AND | | SHOW REQUIRED PROTECTION OF THE TANK AND | | APPURTENANCES PER NFPA 58. IF THE TANK | | IS BELOW GROUND THE CONTAINER SHALL BE | | SECURILY ANCHORED PER NFPA 58 SECTION | | 3-2.2.7(H). | | | | END OF COMMENTS: | | | | REVIEW BY MIKE PERSON | | (561)805-6730 | | FAX (561)805-6731 | | E-MAIL [email protected] | | UNDER SUPERVISION OF K.STEVENS | | (561_805-5621 |
|