Plan Review Notes
Plan Review Notes For Permit 06020373
Permit Number 06020373
Review Stop G
Sequence Number 1
Notes
Date Text
2006-02-10 00:00:00DENIED
 REFERENCE:FBC-2004 FUEL GAS
  
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR GAS PERMIT:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 2. SHOW THE TYPE OF PIPING MATERIAL
 BEING INSTALLED, ALL PIPE SIZES, AND
 TYPE OF REGULATORS.
 3. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
 4. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561)805-6730
 FAX (561)805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561_805-5621