Plan Review Notes For Permit 06020371 |
Permit Number |
06020371 |
|
Review Stop |
G |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-02-10 00:00:00 | DENIED | | REFERENCE:FBC-2004 FUEL GAS | | | | THE FOLLOWING INFORMATION IS REQUIRED | | FOR GAS PERMIT: | | | | 1. INDICATE ON THE DRAWING ALL CUT | | SECTIONS OF PIPE AND CORRESPONDING | | LENGTHS PER FBC-2004 FUEL GAS CODE. THE | | ONLY PIPE INDICATED ON DRAWING IS 20' OF | | 3/4" PE. DROPS AND RISER LENGTHS AND | | TYPE OF MATERIAL BEING USED NEED TO BE | | INDICATED ON DRAWING. ALSOVALVES NEED | | TO BE INDICATED ON DRAWING,THERE NEEDS | | TO BE A SHUT OFF TO GENERATOR. | | 2. NEED SPECS ON GENERATOR, ORIGINAL | | GEN-RES PERMIT APPLICATION DENIED AND | | P/U. THEY NEED TO BE RESUBMITTED AND | | PASSED BY ZONING BEFORE GAS PERMIT CAN | | BE ISSUED. | | 3. LONGEST LENGTH: DRAWING INDICATES 20' | | IS THIS THE LONGEST LENGTH ON SYSTEM? | | EXISTING LOAD IS PART OF SYSTEM. IS THAT | | 20' OR LESS? | | | | END OF COMMENTS: | | | | REVIEW BY MIKE PERSON | | (561)805-6730 | | FAX (561)805-6731 | | E-MAIL [email protected] | | UNDER SUPERVISION OF K.STEVENS | | (561)805-6721 |
|