Plan Review Notes
Plan Review Notes For Permit 06020364
Permit Number 06020364
Review Stop B
Sequence Number 1
Notes
Date Text
2006-02-08 00:00:00DENIED
  
 1) SPECIFY THE MEAN ROOF HEIGHT OF THE
 STRUCTURE.
  
 2) THE MAXIMUM DESIGN PRESSURE FOR THE
 PRODUCT LISTED IN THE NOA IS TOO LOW FOR
 ROOF ZONES 2 AND 3.
  
 3) LIMITATION #1 IN THE NOA ALLOWS
 DESIGN PRESSURES TO BE INCREASED BY
 RATIONAL ANALYSIS BY INCREASING THE
 NUMBER OF FASTENERS. HOWEVER, ALL
 RATIONAL ANALYSIS COMPUTATIONS SHALL BE
 PREPARED, SIGNED AND SEALED BY A FLORIDA
 REGISTERED PROFESSIONAL ENGINEER,
 REGISTERED ARCHITECT OR REGISTERED ROOF
 CONSULTANT.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714