 PLEASE SUBMIT A RISER DIAGRAM INDICATING
 CONDUCTOR,CONDUIT AND GROUNDING
 ELECTRODE SYSTEM SIZES.
 ALSO CHECK THE AVAILABLE FAULT CURRENT
 AT THE TRANSFORMER TO CONFIRM THE
 EQUIPMENT CONFORMS TO 110.9 AND 10.
  
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  