Plan Review Notes For Permit 06020337 |
Permit Number |
06020337 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-02-10 00:00:00 | | | PLEASE SUBMIT A RISER DIAGRAM INDICATING | | CONDUCTOR,CONDUIT AND GROUNDING | | ELECTRODE SYSTEM SIZES. | | ALSO CHECK THE AVAILABLE FAULT CURRENT | | AT THE TRANSFORMER TO CONFIRM THE | | EQUIPMENT CONFORMS TO 110.9 AND 10. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/561) 805-6731 | | |
|