Plan Review Notes
Plan Review Notes For Permit 06020317
Permit Number 06020317
Review Stop B
Sequence Number 3
Notes
Date Text
2006-08-18 00:00:00DENIED
  
  
 1.713.13(2) F.S.THE NOTICE OF
 COMMENCEMENT MUST BE RE-RECORDED BECAUSE
 THE DESCRIBED IMPROVEMENT OR
 CONSTRUCTION DID NOT COMMENCE WITHIN 90
 DAYS OF RECORDING.
  
 3.ADJUST PERMIT VALUE TO REFLECT ALL
 MATERIALS AND LABOR AND PAY ADDITIONAL
 PERMIT FEES.
  
 4.SIGN OWNER/AGENT ON ENERGY CALCS PER
 2004 FBC.
  
 5.SUBMIT TWO COMPLETE SETS OF PRODUCT
 APPROVALS FOR THE FOLLOWING, INSWING
 DOOR, STRAPS AND TIE-DOWNS.
  
 6.JELD-WEN DOOR AND STRAPS AND
 TIE-DOWNS MISSING THE FOLLOWING STATE
 PRODUCT APPROVAL,POMA SHUTTER ON FILE
 HERE OK.
  
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A STATE PRODUCT APPROVAL
 SHEETS THAT LISTS THE PRODUCT IDENTITY
 NUMBER FROM THE STATE. IF THE PRODUCT
 DOES NOT HAVE STATEWIDE APPROVAL, SUBMIT
 AN APPLICATION FOR LOCAL PRODUCT
 APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 7.THOSE PRODUCT APPROVALS WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.WPB
 AMENDMENT TO FBC 106.3.3.PRODUCT
 APPROVALS NOT LISTED ON LETTER.
  
 9.A DESIGN PROFESSIONAL OR AN OWNER
 MUST ELECT ONE OR A COMBINATION OF
 LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
 SHOW HOW PLANS WILL COMPLY WITH THE
 SECTION(S) SELECTED.2004 FBC EXISTING
 BUILDING 301.5
  
  
 A.PROTECTION AGAINST DECAYR319
 2.ALL WOOD FRAMING MEMBERS THAT
 REST ON CONCRETE OR MASONRY EXTERIOR
 FOUNDATION WALLS AND ARE LESS THAN 8
 INCHES FROM THE EXPOSED GROUND.
 3.SILLS AND SLEEPERS ON A CONCRETE
 OR MASONRY SLAB THAT IS IN DIRECT
 CONTACT WITH THE GROUND UNLESS SEPARATED
 FROM SUCH SLAB BY AN IMPERVIOUS MOISTURE
 BARRIER.
 5.WOOD SIDING, SHEATHING AND WALL
 FRAMING ON THE EXTERIOR OF A BUILDING
 HAVING A CLEARANCE OF LESS THAN 6 INCHES
 FROM THE GROUND.
 6.WOOD STRUCTURAL MEMBERS
 SUPPORTING MOISTURE-PERMEABLE FLOORS OR
 ROOFS THAT ARE EXPOSED TO THE WEATHER,
 SUCH AS CONCRETE OR MASONRY SLABS,
 UNLESS SEPARATED FROM SUCH FLOORS OR
 ROOFS BY AN IMPERVIOUS MOISTURE BARRIER.
  
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. SUBMIT ONE COPY OF
 OLD PAGES FOR REFERENCE. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
  
 ART LANGE
 CONSTRUCTION SERVICES DEPARTMENT
 BUILDING PLANS EXAMINER
 561-805-6672