Plan Review Notes
Plan Review Notes For Permit 06020317
Permit Number 06020317
Review Stop P
Sequence Number 1
Notes
Date Text
2006-02-21 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
  
 PLEASE ADJUST YOUR NOTES, DETAILS, OR
 SUBMITTALS TO REFLECT THE FOLLOWING
 INFORMATION REQUIRED FOR PLAN REVIEW:
  
 1. RESIDENTIAL (ONE AND TWO FAMILY)
 PER 601.3.5.4, SUBMIT A PLUMBING
 SANITARY ISOMETRIC RISER DIAGRAM
 INDICATING ALL WASTE, VENTS, AND TRAPS
 WITH SIZES.
 2. SECTION 405 INSTALLATION OF FIXTURES
 405.3.1 WATER CLOSETS, LAVATORIES SHALL
 NOT BE SET CLOSER THAN 15" FROM ITS
 CENTER TO ANY SIDE WALL.(NOTE: FINISHED
 SIDE WALL OR SHOWER STALL WALL) WATER
 CLOSET COMPARTMENTS SHALL NOT BE LESS
 THAN 30" WIDE. THERE SHALL BE AT LEAST
 21" CLEARENCE IN FRONT OF LAVATORY OR
 WATER CLOSET TO ANY WALL, FIXTURE OR
 DOOR.
 417.4 SHOWER COMPARTMENTS. ALL SHOWER
 COMPARTMENTS SHALL HAVE A MINIMUM OF 900
 SQUARE INCHES OF INTERIOR
 CROSS-SECTIONAL AREA. SHOWER
 COMPARTMENTS SHALL NOT BE LESS THAN 30
 INCHES IN MINIMUM DIMENSION MEASURED
 FROM THE FINISHED INTERIOR DIMENSION OF
 THE COMPARTMENT.
 (NOTE: THE ABOVE MEASUREMENTS NEED TO BE
 INDICATED ON DRAWING. THE 5 FOOT INSIDE
 TO INSIDE MEASUREMENT ON YOUR DRAWING
 WILL NOT MEET MINIMUM REQUIREMENTS
 PLEASE REWORK MEASUREMENTS TO COMPLY
 WITH MINIMUM STANDARDS.)
 3. SECTION 917 AIR ADMITTANCE VALVES.
 PLEASE CORRECT DRAWING FROM STUDIO VENT
 TO AIR ADMITTANCE VALVE.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561)805-6730
 FAX (561)805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561)805-6721