Plan Review Notes For Permit 06020239 |
Permit Number |
06020239 |
|
Review Stop |
G |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-02-09 00:00:00 | DENIED | | REFERENCE: FBC-2004 FUEL GAS | | | | THE FOLLOWING INFORMATION IS REQUIRED | | FOR GAS PERMIT: | | | | 1. GAS PIPING SYSTEM IS SIZED | | INCORRECTLY PLEASE SIZE CORRECT USING | | THE FOLLOWING TABLES FROM THE FBC-2004 | | FUEL GAS CODE. | | SCHEDULE 40 METALLIC PIPE - 402.4(2) | | CSST - 402.4(14) | | CSST - FOR GASTITE TABLE 7.1 FROM THE | | GASTITE INSTALLATION MANUAL. | | CSST - TRACKPIPE HAS NO MATCHING TABLE | | POLYETHYLENE PLASTIC PIPE - 402.4(20) | | 2. GALVANIZED PIPE UNDERGROUND NOT | | ALLOWED. | | | | END OF COMMENTS: | | | | REVIEW BY MIKE PERSON | | (561)805-6730 | | FAX(561)805-6731 | | E-MAIL [email protected] | | UNDER SUPERVISION OF K.STEVENS | | (561)805-6721 |
|