Plan Review Notes
Plan Review Notes For Permit 06020239
Permit Number 06020239
Review Stop G
Sequence Number 1
Notes
Date Text
2006-02-09 00:00:00DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR GAS PERMIT:
  
 1. GAS PIPING SYSTEM IS SIZED
 INCORRECTLY PLEASE SIZE CORRECT USING
 THE FOLLOWING TABLES FROM THE FBC-2004
 FUEL GAS CODE.
 SCHEDULE 40 METALLIC PIPE - 402.4(2)
 CSST - 402.4(14)
 CSST - FOR GASTITE TABLE 7.1 FROM THE
 GASTITE INSTALLATION MANUAL.
 CSST - TRACKPIPE HAS NO MATCHING TABLE
 POLYETHYLENE PLASTIC PIPE - 402.4(20)
 2. GALVANIZED PIPE UNDERGROUND NOT
 ALLOWED.
  
 END OF COMMENTS:
  